Specifications

Drive Ratings

Catalog
Number

Output Ratings

Input Ratings

Branch Circuit Protection

kW (HP)

Amps

Voltage

Range

kVA Amps Fuses

140M Motor
Protectors

(1)

(2)

Contactors

Min.

Enclosure

Volume

(3)

(in.

3

)

45°C 50°C

200 - 240V AC – 3-Phase Input, 0 - 230V 3-Phase Output

22C-B012N103

2.2 (3.0)

12

12

180-265 6.5

15.5

20

140M-F8E-C16

100-C23

5098

22C-B017N103

3.7 (5.0)

17.5

17.5

180-265 8.8

21

30

140M-F8E-C25

100-C37

5098

22C-B024N103

5.5 (7.5)

24

24

180-265 10.9 26.1

35

140M-F8E-C32

100-C37

5098

22C-B033N103

7.5 (10)

33

33

180-265 14.4 34.6

45

140M-F8E-C45

100-C45

5098

22C-B049A103

11 (15)

49

49

180-265 21.3 51

70

100-C60

22C-B065A103

15 (20)

65

65

180-265 28.3 68

90

100-C85

22C-B075A103

18.5 (25)

75

75

180-265 32.5 78

100

100-D95

22C-B090A103

22 (30)

90

81

180-265 38.3 92

125

100-D110

22C-B120A103

30 (40)

120

120

180-265 51.6 124

175

100-D180

22C-B145A103

37 (50)

145

130

180-265 62.4 150

200

100-D180

380 - 480V AC – 3-Phase Input, 0 - 460V 3-Phase Output

22C-D6P0N103 2.2 (3.0)

6

6

340-528 6.3

7.5

10

140M-D8E-C10

100-C09

5098

22C-D010N103

4.0 (5.0)

10.5

10.5

340-528 10.9 13

20

140M-D8E-C16

100-C16

5098

22C-D012N103

5.5 (7.5)

12

12

340-528 11.9 14.2

20

140M-D8E-C16

100-C23

5098

22C-D017N103

7.5 (10)

17

17

340-528 15.3 18.4

25

140M-D8E-C20

100-C23

5098

22C-D022N103

11 (15)

22

22

340-528 19.2 23

30

140M-F8E-C32

100-C30

5098

22C-D030N103

15 (20)

30

27

340-528 25.8 31

40

140M-F8E-C32

100-C37

5098

22C-D038A103

18.5 (25)

38

38

340-528 33.3 40

50

140M-F8E-C45

100-C60

9086

22C-D045A103

22 (30)

45.5

45.5

340-528 39.1 47

60

100-C60

22C-D060A103

30 (40)

60

54

340-528 53.3 64

80

100-C85

22C-D072A103

37 (50)

72

72

340-528 60.7 73

100

100-C85

22C-D088A103

45 (60)

88

88

340-528 74.9 90

125

100-D110

22C-D105A103

55 (75)

105

105

340-528 89

107

150

100-D140

22C-D142A103

75 (100)

142

128

340-528 124.8 150

200

100-D180

22C-D170A103

90 (125)

170

170

340-528 142

170

250

100-D250

22C-D208A103

110 (150) 208

208

340-528 167

200

250

100-D250

22C-D260A103

132 (200) 260

260

340-528 196

235

300

100-D300

22C-D310A103

160 (250) 310

290

340-528 242

290

400

100-D420

22C-D370A103

200 (300) 370

370

340-528 304

365

500

100-D420

22C-D460A103

250 (350) 460

410

340-528 387

465

600

100-D630

(1)

The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See

Bulletin 140M

Motor Protection Circuit Breakers Application Ratings

.

(2)

Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240
Wye or Delta, 480Y/277 or 600Y/347. Not UL listed for use on 480V or 600V Delta/Delta, corner
ground, or high-resistance ground systems.

(3)

When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be
installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this
column. Application specific thermal considerations may require a larger enclosure.

Advertising