Accel/Decel Selection

The Accel/Decel rate can be obtained by a variety of methods. The
default rate is determined by P039 [Accel Time 1] and P040 [Decel Time
1]. Alternative Accel/Decel rates can be made through digital inputs,
RS485 (DSI) communications and/or parameters. See the chart below
for the override priority.

RS485 (DSI) Port

Controls Speed

No

Yes

Either

P039 [Accel Time 1]/P040 [Decel Time 1]

or

A147 [Accel Time 2]/A148 [Decel Time 2]

can be selected when

RS485 (DSI) port is active.

Input is programmed

as "Acc & Dec 2"

[Digital Inx Sel] = 18

No

Yes

A147 [Accel Time 2]/A148 [Decel Time 2]

is active when input is active.

Speed is controlled

by [Preset Freq x]

No

Yes

P039 [Accel Time 1]/P040 [Decel Time 1];

A147 [Accel Time 2]/A148 [Decel Time 2]

determined by the active

Preset Frequency.

See A143-A146 [Preset Freq 0-3]

Drive is performing an

Auxiliary Motor AutoSwap

No

Yes

A147 [Accel Time 2]/A148 [Decel Time 2]

are used.

P039 [Accel Time 1]/P040 [Decel Time 1]

are used.