Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 25

Advertising
background image

Installation/Wiring

1-13

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual

Publication 22C-UM001I-EN-P

Table 1.B Recommended Branch Circuit Protective Devices

Voltage
Rating

Drive Rating
kW (HP)

Fuse Rating

(1)

Amps

140M Motor
Protectors

(2)

(3)

Catalog No.

Recommended
MCS Contactors
Catalog No.

Min. Enclosure
Volume

(4)

Inches

3

200-240V
AC –
3-Phase

2.2 (3.0)

20

140M-F8E-C16

100-C23

5098

3.7 (5.0)

30

140M-F8E-C25

100-C37

5098

5.5 (7.5)

35

140M-F8E-C32

100-C37

5098

7.5 (10)

45

140M-F8E-C45

100-C45

5098

11 (15)

70

100-C60

15 (20)

90

100-C85

18.5 (25)

100

100-D95

22 (30)

125

100-D110

30 (40)

175

100-D180

37 (50)

200

100-D180

380-480V
AC –
3-Phase

2.2 (3.0)

10

140M-D8E-C10

100-C09

5098

4.0 (5.0)

20

140M-D8E-C16

100-C16

5098

5.5 (7.5)

20

140M-D8E-C16

100-C23

5098

7.5 (10)

25

140M-D8E-C20

100-C23

5098

11 (15)

30

140M-F8E-C32

100-C30

5098

15 (20)

40

140M-F8E-C32

100-C37

5098

18.5 (25)

50

140M-F8E-C45

100-C60

9086

22 (30)

60

100-C60

30 (40)

80

100-C85

37 (50)

100

100-C85

45 (60)

125

100-D110

55 (75)

150

100-D140

75 (100)

200

100-D180

90 (125)

250

100-D210

110 (150)

250

100-D250

132 (200)

300

100-D300

160 (250)

400

100-D420

200 (300)

500

100-D420

250 (350)

600

100-D630

(1)

Recommended Fuse Class: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.

(2)

The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See

Bulletin 140M

Motor Protection Circuit Breakers Application Ratings

.

(3)

Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240
Wye or Delta, 480Y/277 or 600Y/347. Not UL listed for use on 480V or 600V Delta/Delta, corner
ground, or high-resistance ground systems.

(4)

When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be
installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this
column. Application specific thermal considerations may require a larger enclosure.