Mount the drive upright on a flat, vertical and level surface.

Protect the cooling fan by avoiding dust or metallic particles.

Do not expose to a corrosive atmosphere.

Protect from moisture and direct sunlight.

Maximum Surrounding Air Temperature

Mounting Considerations

Frame

Screw Size

Screw Torque

C

M5 (#10-24)

2.45-2.94 N-m (22-26 lb.-in.)

D

M8 (5/16 in.)

6.0-7.4 N-m (53.2-65.0 lb.-in.)

E

M8 (5/16 in.)

8.8-10.8 N-m (78.0-95.3 lb.-in.)

F

M10 (3/8 in.)

19.6-23.5 N-m (173.6-208.3 lb.-in.)

G

M12 (1/2 in.)

33.5-41.0 N-m (296.5-362.9 lb.-in.)

H

M12 (1/2 in.)

33.5-41.0 N-m (296.5-362.9 lb.-in.)

Frame Enclosure Rating

Temperature
Range

Minimum Mounting
Clearances

C

IP 20/UL Open-Type

-10° to 45°C
(14° to 113°F)

See

Figure 1.1

,

Mounting Option A

IP 30/NEMA 1/UL Type 1

(1)

(1)

Frame C drives require installation of the PowerFlex 400 IP 30/NEMA 1/UL Type 1
option kit to achieve this rating.

-10° to 45°C
(14° to 113°F)

See

Figure 1.1

,

Mounting Option B

IP 20/UL Open-Type

-10° to 50°C
(14° to 122°F)

See

Figure 1.1

,

Mounting Option B

D

IP 30/NEMA 1/UL Type 1

-10° to 45°C
(14° to 113°F)

See

Figure 1.2

E

F

See

Figure 1.3

G

See

Figure 1.4

H