T090, T091, Terminal block group – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual
Page 87: Continued)

Programming and Parameters
3-29
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Terminal Block Group
(continued)
T090 [Sleep Sel]
Related Parameter(s):
,
(with FRN 7.xx and later.)
Selects the operation of the sleep function.
Options
0 “AI1 > SlpLvl” (Default) Sleep enabled from Analog Input 1 (d305 [Analog In 1]) above
sleep level.
1 “AI1 < SlpLvl”
Sleep enabled from Analog Input 1 (d305 [Analog In 1]) below
sleep level.
2 “AI2 > SlpLvl”
Sleep enabled from Analog Input 2 (d306 [Analog In 2]) above
sleep level.
3 “AI2 < SlpLvl”
Sleep enabled from Analog Input 2 (d306 [Analog In 2]) below
sleep level.
4 “OFrq>SlpLvl”
Sleep enabled based on drive output frequency (b001 [Output
Freq]) above sleep level.
5 “OFrq<SlpLvl”
Sleep enabled based on drive output frequency (b001 [Output
Freq]) below sleep level.
6 “CFrq>SlpLvl”
Sleep enabled based on drive command frequency (b002
[Commanded Freq]) above sleep level.
7 “CFrq<SlpLvl”
Sleep enabled based on drive command frequency (b002
[Commanded Freq]) below sleep level.
T091 [Wake Sel]
Related Parameter(s):
,
(with FRN 7.xx and later.)
Selects the operation of the wake function.
Options
0 “AI1 > WakLvl”
(Default)
Wake enabled from Analog Input 1 (d305 [Analog In 1]) above
wake-up level.
1 “AI1 < WakLvl”
Wake enabled from Analog Input 1 (d305 [Analog In 1]) below
wake-up level.
2 “AI2 > WakLvl”
Wake enabled from Analog Input 2 (d306 [Analog In 2]) above
wake-up level.
3 “AI2 < WakLvl”
Wake enabled from Analog Input 2 (d306 [Analog In 2]) below
wake-up level.
4 “CFrq>WakLvl”
Wake enabled based on drive command frequency (b002
[Commanded Freq]) above wake-up level.
5 “CFrq<WakLvl”
Wake enabled based on drive command frequency (b002
[Commanded Freq]) below wake-up level.