Params defaulted, Analog input loss – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 138

Advertising
background image

4-4

Troubleshooting

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

No.

Fault

Ty

p

e

(1

)

Description

Action

F15

Load Loss

Output current has dropped
below the level set in

A184

[Load Loss Level].

Check for load loss (i.e., a broken belt).

F17

Input Phase
Loss (FRN 6.xx
and later)

Excessive DC bus ripple
voltage detected. See

d329

[DC Bus Ripple V].

Check incoming power for a missing
phase or blown fuse. If drive is used
intentionally with single phase input,
apply output derating to 35% actual
drive rating.

F29

Analog Input
Loss

An analog input is configured
to fault on signal loss. A signal
loss has occurred.
Configure with

T072

[Analog In

Loss].

1. Check parameters.
2. Check for broken/loose

connections at inputs.

F32

Fan Fdbck Loss
(FRN 6.xx and
later)

A loss of cooling fan feedback
has been detected. (Frames E
and F only)

Make sure cooling fans are clear of
debris and spinning freely. Replace fan
if necessary.

F33

Auto Rstrt Tries

Drive unsuccessfully
attempted to reset a fault and
resume running for the
programmed number of

A163

[Auto Rstrt Tries].

Correct the cause of the fault and
manually clear.

F38

Phase U to Gnd

A phase to ground fault has
been detected between the
drive and motor in this phase.

1. Check the wiring between the drive

and motor.

2. Check motor for grounded phase.
3. Replace drive if fault cannot be

cleared.

F39

Phase V to Gnd

F40

Phase W to Gnd

F41

Phase UV Short

Excessive current has been
detected between these two
output terminals.

1. Check the motor and drive output

terminal wiring for a shorted
condition.

2. Replace drive if fault cannot be

cleared.

F42

Phase UW Short

F43

Phase VW Short

F48

Params
Defaulted

The drive was commanded to
write default values to
EEPROM.

1. Clear the fault or cycle power to the

drive.

2. Program the drive parameters as

needed.

F63

SW OverCurrent

Programmed

A183

[SW

Current Trip] has been
exceeded.

Check load requirements and

A183

[SW Current Trip] setting.

F64

Drive Overload

Drive rating of 110% for 1
minute or 150% for 3 seconds
has been exceeded.

Reduce load or extend Accel Time.

F70

Power Unit

Failure has been detected in
the drive power section.

1. Cycle power.
2. Replace drive if fault cannot be

cleared.

F71

Net Loss

The communication network
has faulted.

1. Cycle power.
2. Check communications cabling.
3. Check network adapter setting.
4. Check external network status.

(1)

See

page 4-1

for a description of fault types.

Advertising