Programming and Parameters

3-7

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual

Publication 22C-UM001I-EN-P

Basic Program Group

P031 [Motor NP Volts]

Related Parameter(s):

b004

,

A170

,

A171

,

A172

,

A173

Stop drive before changing this parameter.

Set to the motor nameplate rated volts.

Values

Default:

Based on Drive Rating

Min/Max:

20/Drive Rated Volts

Display:

1 VAC

P032 [Motor NP Hertz]

Related Parameter(s):

A170

,

A171

,

A172

,

A173

,

A181

,

A182

Stop drive before changing this parameter.

Set to the motor nameplate rated frequency.

Values

Default:

60 Hz

Min/Max:

15/320 Hz

Display:

1 Hz

P033 [Motor OL Current]

Related Parameter(s):

P042

,

T055

,

T060

,

T065

,

A175

,

A179

,

A180

,

A181

,

A183

Set to the maximum allowable motor current.

The drive will fault on an F7

Motor Overload

if the value of this parameter is exceeded by 150% for 60

seconds.

Values

Default:

Drive Rated Amps

Min/Max:

0.0/(Drive Rated Amps

×

2)

Display:

0.1 Amps

P034 [Minimum Freq]

Related Parameter(s):

b001

,

b002

,

P035

,

T070

,

T074

,

A171

,

A172

,

A173

,

d302

Sets the lowest frequency the drive will output continuously.

Values

Default:

0.0 Hz

Min/Max:

0.0/320.0 Hz

Display:

0.1 Hz

P035 [Maximum Freq]

Related Parameter(s):

b001

,

b002

,

P034

,

T071

,

T075

,

T082

T083

,

T085

,

T086

,

A171

,

A172

,

A173

,

d302

Stop drive before changing this parameter.

Sets the highest frequency the drive will output.

Values

Default:

60.0 Hz

Min/Max:

0.0/320.0 Hz

Display:

0.1 Hz