Advanced Program Group (continued)

A196 [Testpoint Sel]

Related Parameter(s):

d319

Used by Rockwell Automation field service personnel.

Values

Default:

1024

Min/Max:

1024/65535

Display:

1

A197 [Fault Clear]

Related Parameter(s):

b007

,

d307

,

d308

,

d309

Stop drive before changing this parameter.

Resets a fault and clears the fault queue. Used primarily to clear a fault over network communications.

Options

0 “Ready/Idle” (Default)

1 “Reset Fault”

2 “Clear Buffer”

Clears all fault buffers.

A198 [Program Lock]

Protects parameters against change by unauthorized personnel. Enter a user-selected password to
lock the parameters via Option 1. Enter the same password to unlock the parameters.

Options

0 “Unlocked” (Default)

1 “Locked”

Locks all parameters.

2 “Locked”

Parameter edits allowed over communications network.

3 “Locked”

Locks

P035

[Maximum Freq] and

A170

[Boost Select].

A199 [Motor NP Poles]

Related Parameter(s):

d323

Sets the motor poles. This is used to calculate

d323

[Output RPM].

Values

Default:

4

Min/Max:

2/40

Display:

1

A200 [Motor NP FLA]

Related Parameter(s):

A167

Set to the motor nameplate rated full load amps.

Values

Default:

Drive Rated Amps

Min/Max:

0.1/(Drive Rated Amps

×

2)

Display:

0.1 Amps