2-8

Start Up

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

Auto/Manual Mode

In Manual mode:

Start command is defined by

P036

[Start Source].

Speed Reference command is defined by the Digital Speed
Increment and Decrement keys.

Auto key toggles frequency control to AUTO in a bumpless transfer.

In AUTO mode:

Auto key LED is illuminated.

Start command is defined by

P036

[Start Source].

Speed Reference command is defined by

P038

[Speed Reference].

Auto key switches frequency control to the integral keypad in a
bumpless transfer.

Table 2.C P042 [Auto Mode]

=

3 “Auto/Manual”

T051-T054 [Digital Inx Sel]

2 “Auto Mode” or 3 “Local”

Important: Certain digital input settings can override drive operation.

Refer to

Start and Speed Reference Control on page 1-28

for details.

Manual Mode

AUTO Mode

Key

LED Key Function

LED Key Function

Off Not active.

Only active if P036 [Start Source] =
0 “Keypad”. Starts drive.
Runs according to Speed Increment/
Decrement keys.

Off Not active.

Only active if P036 [Start Source] =
0 “Keypad”. Starts drive.

On Changes speed.

Off Not active.

Keys are only active if P038 [Speed
Reference] = 0 “Drive Pot”.

Off Changes to AUTO Mode.

If running, drive will continue to run
at reference defined by P038 [Speed
Reference].

On Changes to Manual Mode.

If running, drive will continue to run
according to Digital Speed
Increment and Decrement keys.

N/A Stops drive.

N/A Stops drive.