3-58

Programming and Parameters

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

Aux Relay Card Group (continued)

R242 [Aux 1 Stop Freq]
R245 [Aux 2 Stop Freq]
R248 [Aux 3 Stop Freq]

Sets the frequency that causes the next running auxiliary motor to turn off.

Values

Default:

25.0 Hz

Min/Max:

0.0/320.0 Hz

Display:

0.1 Hz

R243 [Aux 1 Ref Add]
R246 [Aux 2 Ref Add]
R249 [Aux 3 Ref Add]

Sets the amount to add to the PID reference once the next auxiliary motor is turned on to compensate
for a drop in the pipe due to the increased flow in a typical pump system.

Values

Default:

0.0%

Min/Max:

0.0/100.0%

Display:

0.1%

R250 [Aux Start Delay]

Sets the delay time before turning on the next auxiliary motor once the output frequency has risen
above the value set in [Aux X Start Freq].

Values

Default:

5.0 Secs

Min/Max:

0.0/999.9 Secs

Display:

0.1 Secs

R251 [Aux Stop Delay]

Sets the delay time before turning off the next running auxiliary motor once the output frequency has
dropped below the value set in [Aux X Stop Freq].

Values

Default:

3.0 Secs

Min/Max:

0.0/999.9 Secs

Display:

0.1 Secs

R252 [Aux Prog Delay]

Sets the time delay between connecting the drive controlled motor contactor and running the drive
controlled motor and starting the auxiliary motor control.

Values

Default:

0.50 Secs

Min/Max:

0.00/60.00 Secs

Display:

0.01 Secs