I/o wiring examples, 24 installation/wiring – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 36

Advertising
background image

1-24

Installation/Wiring

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

I/O Wiring Examples

Input/Output

Connection Example

Required Settings

Potentiometer
1-10k Ohm Potentiometer
Recommended
(2 Watt Minimum)

DIP Switch

AI1 = 10V

Parameters

P038 [Speed Reference] = 2 “Analog In1”
T069 [Analog In 1 Sel] = 2 “0-10V”

Scaling

T070 [Analog In 1 Lo]
T071 [Analog In 1 Hi]

Check Results

d305 [Analog In 1]

Analog Input
Bipolar Speed Reference,
±10V Input

DIP Switch

AI2 = 10V

Parameters

P038 [Speed Reference] = 3 “Analog In2”
T073 [Analog In 2 Sel] = 3 “-10 to +10V”

Scaling

T074 [Analog In 2 Lo]
T075 [Analog In 2 Hi]

Check Results

d306 [Analog In 2]

Analog Input
Unipolar Speed Reference,
0 to +10V Input

DIP Switch

AI1 = 10V

Parameters

P038 [Speed Reference] = 2 “Analog In1”
T069 [Analog In 1 Sel] = 2 “0-10V”

Scaling

T070 [Analog In 1 Lo]
T071 [Analog In 1 Hi]

Check Results

d305 [Analog In 1]

Analog Input
Unipolar Speed Reference,
4-20 mA Input

DIP Switch

AI1 = 20MA

Parameters

P038 [Speed Reference] = 2 “Analog In1”
T069 [Analog In 1 Sel] = 1 “4-20 mA”

Scaling

T070 [Analog In 1 Lo]
T071 [Analog In 1 Hi]

Check Results

d305 [Analog In 1]

Analog Output
Unipolar, 0 to +10V Output

1k Ohm Minimum

DIP Switch

AO1 = 10V

Parameters

T082 [Analog Out1 Sel] = 0 through 6

Scaling

T083 [Analog Out1 High]
T084 [Analog Out1 Setpt]

12

13

14

17

18

-/+ 10V

Common

13

14

+

Common

13

14

+

Common

14

15

Common

+

Advertising