26 installation/wiring – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 38

Advertising
background image

1-26

Installation/Wiring

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

2 Wire Control
Sourcing (SRC),
Internal Supply,
Run FWD/Run REV

Input must be active for the
drive to run.

When input is opened, the
drive will stop as specified by
P037 [Stop Mode].

If both Run FWD and Run
REV inputs are closed at the
same time, an undetermined
state could occur.

Drive will not run if I/O
Terminal 01 is open. Drive will
coast to stop if opened while
running.

DIP Switch

SNK/SRC = SRC

Parameters

P036 [Start Source] = 2, 3, 4
P037 [Stop Mode] = 0 through 7
A166 [Reverse Disable] = 0 “Enabled”

2 Wire Control with Function
Loss and SW Enable
Sourcing (SRC),
Internal Supply,
Non-Reversing

Input must be active for the
drive to run.

When input is opened, the
drive will stop as specified by
P037 [Stop Mode].

Drive will not run if I/O
Terminal 03 is open. Drive will
coast to stop if opened while
running.

Drive will fault if I/O Terminal
01 is open. Drive will coast to
stop if opened while running.
Requires drive reset once
terminal is closed.

DIP Switch

SNK/SRC = SRC

Parameters

P036 [Start Source] = 6 “2-W Lvl/Enbl”
P037 [Stop Mode] = 0 through 7

3 Wire Control
Sourcing (SRC),
Internal Supply,
Non-Reversing

A momentary input will start
the drive.

A stop input to I/O Terminal 01
will stop the drive as specified
by P037 [Stop Mode].

DIP Switch

SNK/SRC = SRC

Parameters

P036 [Start Source] = 1 “3-Wire”
P037 [Stop Mode] = 0 through 7

3 Wire Control
Sourcing (SRC),
Internal Supply,
Reversing

A momentary input will start
the drive.

A stop input to I/O Terminal 01
will stop the drive as specified
by P037 [Stop Mode].

I/O Terminal 03 determines
direction.

DIP Switch

SNK/SRC = SRC

Parameters

P036 [Start Source] = 1 “3-Wire”
P037 [Stop Mode] = 0 through 7
A166 [Reverse Disable] = 0 “Rev Enabled”

Input/Output

Connection Example

Required Settings

11

01

02

03

Stop-Run

Forward

Stop-Run

Reverse

Function Loss

Run FWD

SW Enable

11

01

02

03

11

01

02

Stop

Start

11

01

02

03

Stop

Start

Direction

Advertising