Advanced Program Group (continued)

A160 [Process Factor]

Related Parameter(s):

b008

Scales the output frequency value displayed by

b008

[Process Display].

Values

Default:

30.0

Min/Max:

0.1/999.9

Display:

0.1

Output Freq

Process Factor

Process Display

=

x

A163 [Auto Rstrt Tries]

Related Parameter(s):

T055

,

T060

,

T065

,

T066

,

A164

Sets the maximum number of times the drive attempts to reset a fault and restart.
Clear a Type 1 fault and restart the drive.
1. Set A163 [Auto Rstrt Tries] to a value other than “0”.
2. Set

A164

[Auto Rstrt Delay] to a value other than “0”.

Clear an OverVoltage, UnderVoltage or Heatsink OvrTmp fault without restarting the drive.
1. Set A163 [Auto Rstrt Tries] to a value other than “0”.
2. Set

A164

[Auto Rstrt Delay] to “0”.

Note: If the parameter is not set to zero and [Auto Rstrt Time] is set to zero, auto fault clear is enabled.
This feature automatically clears faults, but does not restart the drive.

Values

Default:

0

Min/Max:

0/9

Display:

1

ATTENTION:

Equipment damage and/or personal injury may result if this parameter

is used in an inappropriate application. Do not use this function without considering
applicable local, national and international codes, standards, regulations or industry
guidelines.

A164 [Auto Rstrt Delay]

Related Parameter(s):

A163

Sets the time between restart attempts when

A163

[Auto Rstrt Tries] is set to a value other than zero.

Note: If the parameter is not set to zero and [Auto Rstrt Time] is set to zero, auto fault clear is enabled.
This feature automatically clears faults, but does not restart the drive.

Values

Default:

1.0 Secs

Min/Max:

0.0/160.0 Secs

Display:

0.1 Secs