Example 1
One External Motor without AutoSwap

Auxiliary Motor Control is enabled via Parameter

R239

[Aux Motor Mode].

Number of auxiliary motors is set via Parameter

R240

[Aux Motor Qty].

Relays are configured for Auxiliary Motor Control via parameters

T055

,

T060

,

R222

, and

R225

.

The frequency of Motor #1 that Motor #2 turns on at is set via Parameter

R241

[Aux 1 Start Freq].

The time that Motor #1 is above the value set by

R241

[Aux 1 Start Freq]

before turning on Motor #2 is set via Parameter

R250

[Aux Start Delay].

The frequency of Motor #1 that Motor #2 turns off at is set via Parameter

R242

[Aux 1 Stop Freq].

The time that Motor #1 is below the value set by

R242

[Aux 1 Stop Freq]

before turning off Motor #2 is set via Parameter

R251

[Aux Stop Delay].

PID setup is done via Parameters

A150

through

A159

. See Appendix D for

additional information.

Important: If using auxiliary motor control, ensure that wiring and parameter

configuration are correct before wiring contactor outputs. All relays
on the Auxiliary Relay Card will energize on power-up by default.
Failure to verify proper wiring and parameter configuration can result
in improper motor operation or drive damage.

PID

Reference

Feedback

Drive Relays

Auxiliary Relay Card

M2L

PowerFlex 400

Three-Phase Power

M2L

M1

M2

Frequency

R241 [Aux 1 Start Freq]

R251 [Aux Stop Delay]

R250 [Aux Start Delay]

R242 [Aux 1 Stop Freq]

Time