3-50

Programming and Parameters

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

Advanced Program Group (continued)

A193 [Skip Freq Band 3]

Related Parameter(s):

A192

Determines the bandwidth around

A192

[Skip Frequency 3]. A193 [Skip Freq Band 3] is split applying

1/2 above and 1/2 below the actual skip frequency.
A setting of 0.0 disables this parameter.
Values

Default:

0.0 Hz

Min/Max:

0.0/30.0 Hz

Display:

0.1 Hz

Frequency

Time

Skip Frequency

Command

Frequency

Drive Output
Frequency

Skip Frequency Band

A194 [Compensation]

Enables/disables correction options that may improve problems with motor instability.

Options

0 “Disabled”

1 “Electrical” (Default)

(1)

Some drive/motor combinations have inherent instabilities
which are exhibited as non-sinusodial motor currents. This
setting attempts to correct this condition.

2 “Mechanical”

Some motor/load combinations have mechanical resonances
which can be excited by the drive current regulator. This
setting slows down the current regulator response and
attempts to correct this condition.

3 “Both”

(1)

(1)

Use “Dead Time Compensation” algorithm to minimize flat spots in motor current waveforms. Use
this solution also to achieve motor stability.

A195 [Reset Meters]

Related Parameter(s):

d310

-

d317

Resets the marker that indicates Fault Times and Energy usage.

Options

0 “Ready/Idle” (Default)

1 “Reset MWh”

Also resets kWh marker.

2 “Reset Time”

min, hr, and x10hr