Rockwell Automation 193 Drives and Motion Accelerator Toolkit Quick Start User Manual

Page 156

Advertising
background image

156

Rockwell Automation Publication IASIMP-QS019E-EN-P - August 2013

Chapter 6

System Commissioning

For the Kinetix 5500 drives, apply power as required for your system configuration and observe the two status
indicators.

Module Status Indicator

Network Status Indicator

For the Kinetix 350 drives, apply 120, 240, or 460V AC mains input power to the IPD connector. If logic power
is from (24V DC) back-up power, apply backup power to the BP connector first and then apply input power.

Drive Status Indicators

Condition

Status

Steady Off

No power applied to the drive.

Steady Green

Drive is operational. No faults or failures.

Flashing Green

Standby (drive not configured).

Flashing Red

Major recoverable fault. The drive detected a recoverable fault, for example, an
incorrect or inconsistent configuration.

Steady Red

Major fault. The drive detected a non-recoverable fault.

Flashing Green/Red

Self-test. The drive performs self-test during powerup.

Condition

Status

Steady Off

No power applied to the drive or IP address is not configured.

Flashing Green

Drive connection is not established, but has obtained an IP address.

Steady Green

Drive connection is established. Normal operation.

Flashing Red

Connection timeout. One or more of the connections, for which this drive is the target,
has timed out.

Steady Red

Duplicate IP address. IP address specified is already in use.

Flashing Green/Red

Self-test. The drive performs self-test during powerup.

Status Indicator

Status

Status

Network

Flashing red/green or flashing green

Self-test/no connections

Steady green

Communication is ready

Steady or flashing red

Communication error

Module

Flashing red/green or flashing green

Self-test/standby

Steady green

Operational condition

Steady or flashing red

Drive is faulted

Axis

Flashing red/green, flashing green, flashing amber

Self-test/initialization

Steady green

Operational condition

Steady or flashing red

Drive is faulted

Module Status
Network Status

Kinetix 5500 Servo Drive

Kinetix 350
Status Indicators

Advertising