Update e3 plus add-on profiles, E3 plus overload relay with, Communication auxiliary – Rockwell Automation 193 Drives and Motion Accelerator Toolkit Quick Start User Manual

Page 321: Configuration

Advertising
background image

Rockwell Automation Publication IASIMP-QS019E-EN-P - August 2013

321

Controller, Network, and Device Configuration Without the DMAT Wizard

Appendix G

E3 Plus Overload Relay with Communication Auxiliary Configuration

E3 Plus overload relay configuration applies to E3 Plus overload relays with the 193-DNENCAT
communication auxiliary module, and includes these procedures.

Update E3 Plus Add-On Profiles

Add E3 Plus Devices to your Logix Designer Project

Configure E3 Plus Devices

Update E3 Plus Add-On Profiles

Add-On profiles (AOP) are available for download at the Custom Downloads Add-On Profiles website:

https://download.rockwellautomation.com/esd/download.aspx?downloadid=addonprofiles

Follow these steps to download E3 Plus Add-On profiles.

1.

Login to the Custom Download Add-On Profiles website.

The Custom Download Files dialog box opens.

2.

Check AOP for E3 Plus 193-DNENCAT(R).

3.

Click Download Now and accept the user license agreement.

If prompted to install the Download Manager, allow the installation.

4.

Click the Add-On Profile icon and follow the download instructions.

5.

Extract the AOP zip file and run MPSetup.

IMPORTANT

The E3 Plus Add-On Profiles are independent of RSLogix 5000 software or Logix Designer application releases. Update your E3 Plus
Add-On Profiles to make sure your application runs correctly.