Rockwell Automation 193 Drives and Motion Accelerator Toolkit Quick Start User Manual

Page 282

Advertising
background image

282

Rockwell Automation Publication IASIMP-QS019E-EN-P - August 2013

Appendix G

Controller, Network, and Device Configuration Without the DMAT Wizard

8.

Configure module definitions.

The Module Definition dialog box lets you configure and access drive data beyond standard I/O. Four
examples are shown.

a. Enter major and minor revisions appropriate for your drive hardware.

b. Enter drive rating appropriate for your drive hardware and AC input voltage.

c. Set datalink definitions for the intended drive.

d. Check Use Network Reference.

IMPORTANT

The datalinks listed for their respective drives must be configured exactly as shown for successful faceplate AOI import and
operation. If additional datalinks are required for your application, modifications to the corresponding AOIs may be
required.

IMPORTANT

Use Network Reference must be checked to automatically set the speed reference, DPI™, and start source parameters to
the Ethernet port.

To configure the PowerFlex 525 drive to accept commands and report status via an Ethernet network, set
P046 - [Start Source 1] and P047 - [Speed Reference 1] to EtherNet/IP.