Programming 5 - 28 – Yaskawa E7L Drive Bypass User Manual

Page 120

Advertising
background image

Programming 5 - 28

Options - J, U, V or L

"Serial Communications"; Bypass with PI Control and serial communication for run/stop control and

Setpoint input:
Hand mode speed command from Keypad/Operator.
Auto mode PI Setpoint input signal from serial communication.
Auto mode run/stop command for Drive from serial communication.
Auto mode run/stop command for Bypass from serial communication.

Significant

Parameter Setting

Drive Operational Result

b1-01 = 0: Operator

Speed command source = Keypad/Operator (U1-01)

b5-01 = 1: Enable

Enable PI mode of operation

H1-03 = 6C: Com/Inv Sel 2

A Drive terminal S5 input contact opening (H/O/A = Auto) selects serial com for
both the run/stop command and speed command. A Drive terminal S5 input contact
closure (H/O/A = Hand) allows b1-01 to select Keypad/Operator as the speed

command source. This input contact is closed when H/O/A = Hand.

H1-04 = 19: Disable
Jumpers required:
TB5-5 to TB1-12 and TB1-13 to
TB5-2

A Drive terminal S6 input contact closure disables PI mode.

H3-08 = 0: 0-10 VDC

Drive Terminal A2 is programmed for 0-10 VDC (Note - Control PCB DIP switch
S1-2 must also be OFF)

H3-09 = B: PI Feedback

Drive Terminal A2 function is set to provide PI feedback for closed loop control

H5-02 = Baud Rate

Each protocol requires the baud rate indicated in Table 5.2

H5-07 = RTS Control

Each protocol requires the Request to Send control indicated in Table 5.2

H5-08 = Protocol Selection

Drive communicates via protocol selected. 0: Modbus, 1: N2 or 2: FLN