H1-03, Terminal s5 function, Selection – Yaskawa E7L Drive Bypass User Manual

Page 225: Terminal s5 sel, Forward jog, Reverse jog, Fault reset, Command have been removed, Fast-stop n.o, Fast-stop n.c

Advertising
background image

Parameters A - 13

H1-03

Terminal S5 Function
Selection
Terminal S5 Sel

12: Forward Jog
Closed = drive runs forward at speed command entered into

parameter d1-17

13: Reverse Jog
Closed = drive runs in reverse at speed command entered into

parameter d1-17

14: Fault Reset
Closed = Resets the drive after the fault and the run
command have been removed
15: Fast-Stop N.O.
Closed = Drive decelerates using C1-09, regardless of run

command status

17: Fast-Stop N.C.
Closed = Normal operation
Open = Drive decelerates using C1-09, regardless of run

command status

18: Timer Function
Input for independent timer, controlled by b4-01 and b4-02.
Used in conjunction with a multi-function digital output.
19: PI Disable
Turns off the PI controller, and PI setpoint becomes speed

command

1B: Program Lockout
Closed =All parameter settings can be changed.
Open = Only speed command at U1-01 can be changed.
1C: TrimCtl Increase
Closed = Increase motor speed by value in d4-02.
Open = Return to normal speed command.
Not effective when using d1-01 thru d1-04 as a speed

command.

Must be used in conjunction with Trim Ctrl Decrease.
1D: Trim Ctl Decrease
Closed = Decrease motor speed by value in d4-02
Open = Return to normal speed command.
Not effective when using d1-01 thru d1-04 as speed command.
Must be used in conjunction with Trim Ctrl Increase.

0 to 6E

3: 2-wire
0: 3-wire

Programming

Table A.1 Parameter List (Continued)

Parameter

No.

Parameter Name

LCD Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location