F6-05 current scaling via communication option pcb, H1 digital inputs, H1-01 drive terminal s3 function selection – Yaskawa E7L Drive Bypass User Manual

Page 141

Advertising
background image

Programming 5 - 49

F6-05 Current Scaling via Communication Option PCB

A communication option card can read the Drive’s DPRAM to access the current monitor. The format of the current reading in
the DPRAM will be determined by parameter F6-05.

F6-05= “0: A Display” Current is a decimal number corresponding to actual Amperes
F6-05= “1: 100%/8192 (Drive Rated Current)” Current reading is a number where

8192 = 100% of Drive rated output current

H1 Digital Inputs

H1-01 Drive Terminal S3 Function Selection
H1-02 Drive Terminal S4 Function Selection
H1-03 Drive Terminal S5 Function Selection
H1-04 Drive Terminal S6 Function Selection
H1-05 Drive Terminal S7 Function Selection

Setting Range:

0 to 6E

Factory Default: H1-01= “70: Bypass Drv Envl” This is one of the special parameter settings required by the Bypass logic

circuit. See Table 5.1.

H1-02= This is one of the special parameter settings required by the Bypass logic circuit. See Table 5.2
H1-03= This is one of the special parameter settings required by the Bypass logic circuit. See Table 5.2.
H1-04= “4: Multi-Step Ref 2” (2 Wire)

“3: Multi-Step Ref 1” (3 Wire)

H1-05= “6: Jog Freq Ref ” (2 Wire)

“4: Multi-Step Ref 2” (3 Wire)

Setting

Description

0

A Display (factory default)

1

100%/8192 (Drive Rated Current)