Apogee fln logical analog input (lai) summary, Point number, Communications d - 23 – Yaskawa E7L Drive Bypass User Manual

Page 275

Advertising
background image

Communications D - 23

APOGEE FLN Logical Analog Input (LAI) Summary

Table D.14 APOGEE FLN Application 2721 Logical Analog Input (LAI) Summary (Drive to APOGEE FLN)

Point

Number

Database Descriptor

Units

Slope

Intercept

Default

Min

Max

Drive

Parameter

3

FREQ OUTPUT

HZ

0.01

0

0

Fmin

Fmax

U1-02

4

PCT OUTPUT

PCT

0.01

0

0

0

100

5

SPEED

RPM

1

0

0

Fmin

Fmax

6

CURRENT

AMPS

0.01 or 0.1

0

0

0

DriveMax

U1-03

7

TORQUE

PCT

0.1

0

0

0

300

8

POWER

KW

0.1

0

0

0

100

U1-08

9

DRIVE TEMP

DEG F

1

0

DrvTemp

0

4000

U1-41

10

DRIVE KWH

KWH

0.1 or 1

kVA Dep

0

0

0

32767

U1-29

11

DRIVE MWH

MWH

1

0

0

0

32767

U1-30

12

RUN TIME

HR

1

0

0

0

32767

U1-13

13

DC BUS VOLT

VOLTS

1

0

kVA Dep

0

4000

U1-07

14

AC OUT VOLT

VOLTS

1

0

0

0

kVA Dep

U1-06

15

DRV RATED AMP

AMPS

0.01 or 0.1

0

0

0

kVA Dep

n9-01

16

RUN TIME x 10K

10K HR

1

0

0

0

32767

U1-13

17

FAULT CODE

ERR CD

1

0

0

0

U2-01

62

PID FEEDBACK

HZ

0.01

0

0

0

40

U1-24

66

LST FLT CODE

1

0

0

U2-02

67

FREF.FLT

HZ

0.01

0

0

0

400

U2-03

68

OUT FREQ.FAULT

HZ

0.01

0

0

0

400

U2-04

69

OUT CUR.FLT

AMPS

0.1

0

0

0

kVA Dep

U2-05

71

RD PARAM DAT

1

0

75

OUT VOLT.FLT

VOLTS

0.1

0

0

0

400

U2-07

76

DC BUS.FLT

VOLTS

1

0

0

0

4000

U2-08

77

OUT PWR.FLT

KW

0.1

0

0

0

400

U2-09

79

PID DEVIATE

PCT

0.01

0

0

0

400

U1-36

87

PID OUT CAP

PCT

0.01

0

0

0

40

U1-37

88

PID REF

PCT

0.01

0

0

0

40

U1-38

89

COM ERR CD

1

0

0

0

4000

U1-39

99

ERROR STATUS

1

0

0

0

255

Advertising