Diagnostic & Troubleshooting 6 - 15

OV

DC Bus Overvolt

(Flashing)

DC Bus Overvoltage
208-240VAC: Trip point is

≥ 400Vdc

480VAC: Trip point is

≥ 800Vdc

High input voltage at R/L1,
S/L2 and T/L3.

Check the input circuit and
reduce the input power to within
specifications.

Extend the time in C1-02.

The deceleration time is set too
short.

Power factor correction
capacitors are being used on the
input to the Drive.

Remove the power factor correc-
tion capacitors.

OVRD

Emergcy
Override

Emergency Override
Emergency Override is active

Forward or Reverse Emergency
Override input is closed

- - -

PRHT

Motor Preheating

Motor Preheating
Motor is preheating

Motor Preheat 2 input is closed

- - -

UV

DC Bus Undervolt

(Flashing)

DC Bus Undervoltage
The DC bus voltage is

≤ L2-05

208-240VAC: Trip point is

≤ 190Vdc

480VAC: Trip point is

≤ 380Vdc

Low input voltage at R/L1, S/L2
and T/L3.

Check the input circuit and
increase the input power to
within specifications.

The acceleration time is set too
short.

Extend the time in C1-01.

Voltage fluctuation of the input
power is too large.

Check the input voltage.

UV2

CTL PS Undervolt

Control Power Supply Undervoltage of the
control circuit when running

External load connected pulling
down the Drive power supplies.

Cycle power off and on to the
Drive.

Repair or replace the Power PCB/
Gate Drive PCB.

UV3

MC Answerback

Soft Charge Circuit Fault
The pre-charge contactor opened while the
Drive was running.

Contacts on the soft charge
contactor are dirty and the soft
charge contactor does not
function mechanically.

Cycle power off and on to the
Drive.

Check the condition of the soft
charge contactor.

Table 6.4 Alarm Displays and Processing (Continued)

Digital

Operator Display

Description

Cause

Corrective Action