Electrical Installation 2 - 18

Bypass Controller PCB

Fig 2.11 Bypass Control Circuit Inputs and Outputs

* Terminal TB1(9) of the electronic bypass control PCB is only for use in the “Internal Supply 120VAC Logic”, terminals

TB1(1) through TB1(5) as shown above. Terminal TB1(9) should not be used for powering external devices.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

1

2

3

4

5

6

4

3

1

2

4

2

3

1

AC

+V

FM

+

-

SHIELD

ISOLATED

4-20MADC

OR

0-10VDC

AUTO MODE

SPEED

REFERENCE

INPUT

6

9

8

7

5

4

3

2

1

REMOTE TRANSFER

SMOKE PURGE

SPARE

6

9

8

7

5

4

3

2

1

TB1

TB2

TB3

TB1

TB1

MIN. RATING

OF CONTACTS:

MIN. RATING

OF CONTACTS:

CN103

A1/A2 FACTORY SETTING IS 4-20mA CONNECTED TO

DRIVE TERMINAL A2 (AS SELECTED BY DIP SWITCH

S1(2), (3) & (4))

OR

INTERNAL SUPPLY

120 VAC LOGIC

CUSTOMER SUPPLIED

120 VAC LOGIC

A2

PROGRAMMABLE

RELAY #1

MOTOR

RUN

5MA, 120VAC

5MA, 120VAC

120VAC

+/- 15%,

25MA MIN.,

4MA MAX.

LEAKAGE

CURRENT

120VAC COMMON

7

8

9

6

5

4

3

2

1

PE

USER SUPPLY COMMON

ELECTRONIC BYPASS

CONTROL PCB

S+

S-

R+

R-

1

2

3

J1

J1

3

2

1

DRIVE

TERMINAL

S7 INPUT
DRIVE

TERMINAL

S6 INPUT

AC

AM

+V

(+15VDC, 20mA)

A2

4-20MADC OR 0-10VDC

(AS SELECTED BY

DIP SW. S1(2).

FACTORY SETTING IS

4-20MADC)

TB5

TB4

DRIVE AM MONITOR OUPUT

4-20MADC OR 0-10VDC

(AS SELECTED BY JUMPER J3.

FACTORY SETTING IS 4-20MADC)

PROGRAMMABLE

RELAY #2

PROGRAMMABLE

RELAY #3

(FACTORY SETTING

IS SYSTEM FAULT)

(FACTORY SETTING)

ELECTRONIC BYPASS

CONTROL PCB

ELECTRONIC BYPASS

CONTROL PCB

SAFETY INTERLOCKS

(+15VDC,

20mA)

3

2

4-20

MADC

1

3

2

0-10

VDC

1

J2

J3

(AS SELECTED BY

DIP SWITCH S1 (2, 3, & 4).

SEE SH. 2, TABLE 4.

FACTORY SETTING

IS 4-20MADC,

CONNECTED TO DRIVE

ANALOG INPUT 2 (A2).)

BAS/DAMPER INTERLOCK

AUTO MODE RUN/STOP

(FACTORY SETTING

IS HAND MODE)

(FACTORY SETTING

IS AUTO MODE)

FACTORY SETTINGS

TB3(4)

FM

AM

TB5(6)

DRIVE

TERMINAL

SN

DRIVE

TERMINAL

SP

NOT

USED

SEE THE

APPROPRIATE

TECHNICAL

MANUAL FOR

NETWORK

CONNECTIONS

OPTIONS

J, U OR V

SERIAL

COMMUNICATIONS

METASYS (J),

APOGEE (U) OR,

RS 422/485

MODBUS (V)

DRIVE FM MONITOR OUTPUT

4-20MADC OR 0-10VDC

(AS SELECTED BY JUMPER J2.

FACTORY SETTING IS 4-20MADC)

*