Table 1.3 240v enclosure data, Physical installation 1 - 4 – Yaskawa E7L Drive Bypass User Manual

Page 16

Advertising
background image

Physical Installation 1 - 4

Table 1.3 240V Enclosure Data

Input
Volts

HP

1

Drive

Model

CIMR-

Bypass

2

Model

Number

NEC

FLA

OL

110%
1 min

Heat

3

Loss

Watts

Enclosure Dimensions

4

NEMA 1 & NEMA 12 -FVFF

H W D

inches

Weight

5

of

Assembly

Electrical

Schematic

240

0.5

E7U22P21

E7L_A002

2.2

2.4

68

29.48 19.06 13.66

Dimension Drawing

6

S-5537

115 lbs

E7L-00

0.75

E7U22P21

E7L_A003

3.2

3.5

68

1

E7U22P21

E7L_A004

4.0

4.4

78

2

E7U22P21

E7L_A006

6.8

7.5

110

3

E7U22P21

E7L_A009

9.6

10.6

141

5

E7U23P71

E7L_A015

15.2

16.7

202

7.5

E7U25P51

E7L_A022

22.0

24.2

273

10

E7U27P51

E7L_A028

28.0

30.8

365

127 lbs

15

E7U20111

E7L_A042

42.0

46.2

578

20

E7U20151

E7L_A054

54.0

59.4

653

40.48 25.63 14.66

Dimension Drawing

6

S-5539

208 lbs

25

E7U20181

E7L_A068

68.0

74.8

746

30

E7U20221

E7L_A080

80.0

88.0

939

221 lbs

Note 1: Horsepower rating is based on a standard NEMA B 4-pole motor.

Note 2: The underscore position in these model numbers codes for the enclosure type: V = NEMA1, B = NEMA12 FVFF.

Note 3: Heat loss is the amount of heat dissipated by the drive at full load with all standard options available inside the enclosure. Drive heat sink losses are

included in the heat loss data.

Note 4: Height dimension (H) excludes the mounting screw tabs. Depth dimension (D) excludes the disconnect handle.

Note 5: This data represents the total weight with all possible standard options. Weight could be less depending on the options specified.

Note 6: All standard options are available in this size enclosure.

Advertising