L4 speed command loss detection, L4-05 frequency reference loss detection selection – Yaskawa E7L Drive Bypass User Manual

Page 156

Advertising
background image

Programming 5 - 64

L4 Speed Command Loss Detection

L4-05 Frequency Reference Loss Detection Selection

L4-06 Frequency Reference at Loss of Frequency Reference

Setting Range:

0.0 to 100.0% of previous speed command

Factory Default: 80.0% of previous speed command

The Drive can be configured to compensate for the loss of its external speed command. An external speed command is
considered lost if it drops 90% of its value in 400mS or less.

Fig 5.34 Loss of Frequency Reference Timing Diagram

To enable Frequency loss detection, set L4-05= “1: Enabled @ % of PrevRef”. If Frequency Reference Loss Detection is
enabled and the reference is lost, the Drive continues to operate at the speed commanded by parameter L4-06. When the speed
command returns, the Drive again follows the speed command.

Setting H2-01/H2-02= “C: Loss of Ref”, configures a digital output as a Frequency Reference Loss indication only when
L4-05= “1: Enabled @ % of PrevRef”.

Setting

Description

0

Disabled (factory default)

1

Enabled @ % of PrevRef

t

Frequency

Reference

Output

Frequency

t

10%

T

L4-06

100%

T = 400mS

100%

10%

TIME