B5-17 pi accel/decel time, B5-18 pi setpoint selection, B5-19 pi setpoint value – Yaskawa E7L Drive Bypass User Manual

Page 125: B5-20 pi setpoint display scaling

Advertising
background image

Programming 5 - 33

b5-17 PI Accel/Decel Time

Setting Range:

0.0 to 25.5 Seconds

Factory Default: 0.0 Seconds

This is a soft start function that is applied to the PI setpoint analog input. Instead of having nearly instantaneous changes in

signal levels, there is a programmed ramp applied to level changes. When changing setpoints the error can be limited by

gradually ramping the setpoint through the use of parameter b5-17.

b5-18 PI Setpoint Selection

In order to use parameter b5-19 as the PI Setpoint, set parameter b5-18= “1: Enabled”. If b5-18= “0: Disabled” the PI Setpoint
will either be:

Modbus Register 06H (If Register 0FH bit 1 is high)

The active speed command (i.e. Determined by the setting of b1-01). See Table 5.7 “Setpoint Options”

b5-19 PI Setpoint Value

Setting Range:

0.00 to 100.00%

Factory Default: 0.00%

Parameter b5-19 is for a PI Setpoint value. When b5-18= “1: Enabled”, the value of b5-19 will take precedent over any other PI
setpoint unless the Drive is set up for Differential Feedback, in which case, b5-18 and b5-19 have no affect on the PI
function.

b5-20 PI Setpoint Display Scaling

The PI Setpoint Display Scaling value (b5-20) is a scaling factor that is applied to the monitor display for both the PI Setpoint
(U1-38) and the PI Feedback (U1-24).

Setting

Description

0

Disabled (factory default)

1

Enabled

Setting

Description

0

Hz (factory default)

1

%

3

RPM (Synchronous)

3

Engineering Units

Table 5.7 PI Setpoint Display Scaling Options

If b5-20 is:

U1-24 and U1-38

Display Increments.

0

0.01 Hz

1

0.00%

2 through 39

(enter the # of motor poles)

0 RPM

40 through 39999

Engineering Units