Table 1.4 480v enclosure data, Bypass unit enclosures, Nema type 1 enclosures – Yaskawa E7L Drive Bypass User Manual

Page 17: Nema type 12 fvff enclosures, Physical installation 1 - 5

Advertising
background image

Physical Installation 1 - 5

Bypass Unit Enclosures

All Bypass units are intended for non-hazardous locations. Various enclosure types are provided to protect against the applica-
tion environmental conditions:

Nema Type 1 Enclosures

These are constructed for indoor use to provide a degree of protection against incidental contact with enclosed electrical equip-
ment and falling dust or dirt.

NEMA Type 12 FVFF Enclosures

NEMA provides for both non-ventilated and ventilated NEMA 12 enclosures. When ventilated, a suffix to the type number
defines the ventilation method. A NEMA 12 FVFF enclosure has Forced Ventilation with inlet air Filter and outlet air Filter.
The internal pressure is positive with respect to the ambient pressure. UL does not recognize NEMA 12 ventilated enclosures,
therefore, these enclosures are designated NEMA 1 for UL purposes.

Table 1.4 480V Enclosure Data

Input
Volts

HP

1

Drive

Model

CIMR-

Bypass

2

Model

Number

NEC

FLA

OL

110%
1 min

Heat

3

Loss

Watts

Enclosure Dimensions

4

NEMA 1 & NEMA 12 -FVFF

H W D

inches

Weight

5

of

Assembly

Electrical

Schematic

480

0.5

42P21

E7L_B001

1.1

1.2

57

29.48 19.06 13.66

Dimension Drawing

6

S-5537

115 lbs

E7L-00

0.75

42P21

E7L_B001

1.6

1.8

57

1

42P21

E7L_B002

2.1

2.3

62

2

42P21

E7L_B003

3.4

3.7

89

3

42P21

E7L_B004

4.8

5.3

121

5

43P71

E7L_B007

7.6

8.4

155

7.5

45P51

E7L_B011

11.0

12.1

217

10

47P51

E7L_B014

14.0

15.4

318

127 lbs

15

40091

E7L_B021

21.0

23.1

404

20

40111

E7L_B027

27.0

29.7

408

142 lbs

25

40151

E7L_B034

34.0

37.4

485

30

40181

E7L_B040

40.0

44.0

618

40

40241

E7L_B052

52.0

57.2

1040

40.48 25.63 14.66

Dimension Drawing

6

S-5539

203 lbs

50

40301

E7L_B065

65.0

71.5

1045

232 lbs

60

40371

E7L_B077

77.0

84.7

1197

Note 1: Horsepower rating is based on a standard NEMA B 4-pole motor.

Note 2: The underscore position in these model numbers codes for the enclosure type: V = NEMA1, B = NEMA12 FVFF.

Note 3: Heat loss is the amount of heat dissipated by the drive at full load with all standard options available inside the enclosure. Drive heat sink losses are

included in the heat loss data.

Note 4: Height dimension (H) excludes the mounting screw tabs. Depth dimension (D) excludes the disconnect handle.

Note 5: This data represents the total weight with all possible standard options. Weight could be less depending on the options specified.

Note 6: All standard options are available in this size enclosure.

Advertising