Motor overload, L1-01, Motor overload protection – Yaskawa E7L Drive Bypass User Manual

Page 231: Selection, Mol fault select, Disabled, Std fan cooled (enabled), Std blower cooled, Vector motor, 0 to 1

Advertising
background image

Parameters A - 19

Motor Overload

L1-01

Motor Overload Protection
Selection
MOL Fault Select

Enables or disables the motor thermal overload

protection.

0: Disabled
1: Std Fan Cooled (Enabled)
2: Std Blower Cooled
3: Vector Motor

0 to 1

1

Programming

L1-02

Motor Overload Protection
Time
MOL Time Const

Determines how much time will elapse prior to a motor
overload fault (OL1), when motor amps exceed the
value set in parameter E2-01 by 10%. Actual (OL1) trip
time will vary depending on severity of overload.

0.1 to 20.0

8.0min

Programming

L1-03

Motor Overheat Alarm Operation
Selection
Mtr OH Alarm Sel

Operation selection when the motor temperature analog
input (H3-09=E) exceeds the OH3 alarm level (1.17V)
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

3

Programming

L1-04

Motor Overheat Fault Operation
Selection
Mtr OH Fault Sel

Stopping method when the motor temperature analog
input (H3-09=E) exceeds the OH4 level (2.34V).
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop

0 to 2

1

Programming

L1-05

Motor Temperature Input Filter
Time
Mtr Temp Filter

Delay Time applied to motor temperature analog input
(H3-09=E) for filtering purposes.

0.00 to

10.00

0.20sec

Programming

PwrLoss Ridethru

L2-01

Momentary Power Loss Detection
Selection
PwrL Selection

Enables and disables the momentary power loss
function.
0: Disabled - Drive trips on (UV1) fault when power is

lost.

1: PwrL Ride Thru t - Drive will restart if power returns

within the time set in L2-02.*

2: CPU Power Active - Drive will restart if power

returns prior to internal power supply shut down.*

* In order for a restart to occur, the run command must

be maintained throughout the ride thru period.

0 to 2

2

Programming

L2-02

Momentary Power Loss Ride-thru
Time
PwrL Ridethru t

Determines the power loss ride-thru time. This value is
dependent on the capacity of the drive. Only effective
when L2-01 = 1.

0.0 to

25.5sec

kVA

Dependent

Programming

L2-03

Momentary Power Loss Mini-
mum Base Block Time
PwrL Baseblock t

Used to allow the residual motor voltage to decay before
the drive output turns back on. After a power loss, if
L2-03 is greater than L2-02, operation resumes after the
time set in L2-03.

0.1 to 5.0sec

kVA

Dependent

Programming

L2-04

Momentary Power Loss Voltage
Recovery Ramp Time
PwrL V/F Ramp t

The time it takes the output voltage to return to the
preset V/f pattern after speed search (current detection
mode) is complete.

0.0 to 5.0sec

kVA

Dependent

Programming

L2-05

Undervoltage Detection
Level
PUV Det Level

Sets the drive's DC Bus undervoltage trip level. If this is
set lower than the factory setting, additional AC input
reactance or DC bus reactance may be necessary.

Voltage

Class

Dependent

Voltage

Class

Dependent

Programming

Table A.1 Parameter List (Continued

)

Parameter

No.

Parameter Name

LCD Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location