Metasys N2 Binary Input (BI) Summary

Metasys N2 Binary Output (BO) Summary

Table D.11 Metasys N2 Binary Input Summary (E7 to Metasys N2)

Object ID

Object Name

Default

Off (0) State

On (1) State

BI 1

RUN / STOP MONITOR

0

STOPPED

RUNNING

BI 2

FORWARD / REVERSE MONITOR

0

FORWARD

REVERSE

BI 3

DRIVE READY MONITOR

0

NOT READY

READY

BI 4

FAULT MONITOR

0

NOT FAULTED

FAULTED

BI 5

ZERO SPEED

0

NOT ZERO SPEED

ZERO SPEED

BI 6

SPEED AGREE

0

NOT SPEED AGREE

SPEED AGREE

BI 7

MINOR FAULT

0

NO MINOR FAULT

MINOR FAULT

BI 8

MAJOR FAULT

0

NO MAJOR FAULT

MAJOR FAULT

BI 9

DRIVE COMMUNICATION

ERROR MONITOR

0

NO ERROR

ERROR

BI 10

MULTI-FUNCTION OUTPUT 1 (H2-01)

0

-

-

BI 11

MULTI-FUNCTION OUTPUT 2 (H2-02)

0

-

-

BI 12

MULTI-FUNCTION OUTPUT 3 (H2-03)

0

-

-

BI 13

SAFETY INTERLOCK MONITOR

0

SAFETY CLEAR

TERMINAL 3 CLOSED

SAFETY SET

TERMINAL 3 OPEN

BI 14

HAND / AUTO REFERENCE MONITOR

0

REMOTE

LOCAL

BI 15

MULTI-FUNCTION INPUT 1 MONITOR

0

OFF

ON

BI 16

MULTI-FUNCTION INPUT 2 MONITOR

0

OFF

ON

BI 17

MULTI-FUNCTION INPUT 3 MONITOR

0

OFF

ON

BI 18

MULTI-FUNCTION INPUT 4 MONITOR

0

OFF

ON

BI 19

MULTI-FUNCTION INPUT 5 MONITOR

0

OFF

ON

Table D.12 Metasys N2 Binary Output Summary (Metasys N2 to E7)

Object ID

Object Name

Default

Off (0) State

On (1) State

BO 1

RUN FORWARD COMMAND

0

STOP

FORWARD

BO 2

RUN REVERSE COMMAND

0

STOP

REVERSE

BO 3

SERIAL FAULT (EF0) COMMAND

0

NO FAULT

FAULT

BO 4

FAULT RESET COMMAND

0

NO RESET

RESET

BO 5

MULTI-FUNCTION INPUT 1 (H1-01)

0

-

-

BO 6

MULTI-FUNCTION INPUT 2 (H1-02)

0

-

-

BO 7

MULTI-FUNCTION INPUT 3 (H1-03)

0

-

-

BO 8

MULTI-FUNCTION INPUT 4 (H1-04)

0

-

-

BO 9

MULTI-FUNCTION INPUT 5 (H1-05)

0

-

-

BO 10

PANEL LOCK

0

LOCAL/REMOTE AND

STOP/RESET KEYS

ENABLED

LOCAL/REMOTE AND

STOP/RESET KEYS

DISABLED

BO 11

COMMUNICATION FAULT ENABLE

0

EF0 NOT ACTIVATED IF

CABLE LOSS OCCURS

EF0 ACTIVATED IF

CABLE LOSS OCCURS