Diagnostic & Troubleshooting 6 - 10

LL3

Loss of Load Det 1

Loss of Load Detection 1
Drive output current < L6-02 for more than
the time set in L6-03

Motor is underloaded.

Ensure the values in L6-02 and
L6-03 are appropriate.

Check application/machine
status to eliminate fault.

OC

Over Current

Overcurrent
Drive output current exceeded the
overcurrent detection level (approximately
180% of Drive rated output current).

Shorted Drive output phase to
phase, shorted motor, locked
rotor, load too heavy, accel/
decel time too short, contactor
on the Drive output is opened
and closed, a special motor or
a motor with a FLA rating
larger than Drive rated output
current.

Remove the motor and run the
Drive without the motor.

Check the motor for a phase-to-
phase short.

Check the Drive for a phase-to-
phase short at the output.

Verify C1-01 and C1-02 are set
correctly.

Check load conditions.

OH1

Heatsnk MAX Temp

Cooling Fin/Cooling Fin Fan Overheat
The temperature of the Drive cooling fin

exceeded the temperature programmed in
parameter L8-02, and L8-03 = 0-2.

Cooling fan(s) are not
working, high ambient
temperature, a heat source is
too close to the Drive.

Check for dirt build-up on the
fans and cooling fins.

Reduce the ambient temperature
around the Drive.

Drive Internal Cooling Fan

Remove the heating unit. Replace
the cooling fan.

OH3

Motor Overheat 1

Motor Overheating Alarm
The Drive stops or continues operation
according to the setting of L1-03.

Overheating of motor as
measured by motor thermistor.

Recheck the cycle time and the
size of the load.

Recheck the accel/decel time
(C1-01 and C1-02).

Recheck the V/F pattern (E1-01
thru E1-13).

Recheck the motor rated current
value (E2-01).

OH4

Motor Overheat 2

Motor Overheating Fault
The Drive stops operation according to the
setting of L1-04.

Overheating of motor as
measured by motor thermistor.

Recheck the cycle time and the
size of the load.

Recheck the accel/decel time
(C1-01 and C1-02).

Recheck the V/F pattern (E1-01
thru E1-13).

Recheck the motor rated current
value (E2-01).

OL1

Motor Overloaded

Motor Overload
Designed to protect the motor

Fully adjustable from parameter E2-01

The load is too large. The
cycle time is too short at the
accel/decel time.

Recheck the cycle time and the
size of the load as well as the
times set in C1-01 and C1-02.

The voltage of the V/F pattern
is high.

Review the V/F pattern
parameters, E1-01 thru E1-13.

Motor rated current setting is
improper.

Check the motor rated current
value in E2-01.

Table 6.3 Fault Displays and Processing (Continued)

Digital

Operator Display

Description

Cause

Corrective Action