Dip switch programmable functions summary, Auto transfer to bypass, Power up mode – Yaskawa E7L Drive Bypass User Manual

Page 49: Electrical installation 2 - 17

Advertising
background image

Electrical Installation 2 - 17

DIP Switch Programmable Functions Summary

Auto Transfer to Bypass

When enabled (DIP switch S2-1 ON), the Bypass unit will automatically switch into Bypass mode on a Drive fault. After
clearing the Drive fault condition, the function resets by moving the disconnect switch to the OFF position and waiting for the
keypad to go blank. CAUTION: Before selecting this function in fan applications, care must be taken to ensure that the

ductwork is designed to handle the pressure resulting from full speed operation with the VAV terminal unit dampers at

minimum position or closed. The factory default for this function is disabled.

Power Up Mode

The Drive/Bypass electronic interface can be configured (via a DIP switch) to be in the AUTO mode or OFF when power is
applied to the unit. This function is controlled by DIP switch S2-2, ON for AUTO operation on power up. The factory default
is to power up to the OFF mode.

1

2
3
4
3
4

1

2
3
4
5
6

7

4-6

1-6

8

S1

ON

OFF

IN

OUT

FACTORY

SETTING

4-20MADC

0-10VDC

ON
ON

OFF

YES

YES
YES

YES

YES

NO

INACTIVE

ACTIVE

INACTIVE

ACTIVE

DIP

SWITCH

SETTINGS

DESCRIPTION

S2

S3

S4

POS.

SAFETY INTERLOCKS AT TB1(1)
BAS/DAMPER INTERLOCKS AT TB1(3)

TB3(3) CONNECTED TO DRIVE ANALOG INPUT 2 (A2)

TB3(3) CONNECTED TO DRIVE ANALOG INPUT 1 (A1)

DRIVE ANALOG INPUT 2 (A2) SIGNAL (H3-08="0", FOR 0-10VDC)

1

2

AUTO TRANSFER TO BYPASS UPON A DRIVE FAULT

OFF

AUTO

OFF

OFF

ACTIVE

ACTIVE

ACTIVE
ACTIVE
ACTIVE
ACTIVE

ACTIVE

INACTIVE

OFF

OFF

OFF

OFF
OFF

OFF
OFF

OFF

INACTIVE

INACTIVE

INACTIVE
INACTIVE
INACTIVE
INACTIVE

POWER UP IN THE "OFF" OR "AUTO" MODE

3

POWER UP IN THE MAINTENANCE MODE
SEE TABLE 2.6

SEE TABLE 2.6
RESERVED FOR FUTURE EXPANSION MUST BE AT FACTORY SETTING
SPEED COMMAND FROM DRIVE TERMINAL A2, WITH SERIAL COMM.
RESERVED FOR FUTURE EXPANSION MUST BE AT FACTORY SETTING
RESERVED FOR FUTURE EXPANSION MUST BE AT FACTORY SETTING
RESERVED FOR FUTURE EXPANSION MUST BE AT FACTORY SETTING
RESERVED FOR FUTURE EXPANSION MUST BE AT FACTORY SETTING

SERIAL COMMUNICATIONS TERMINATING RESISTANCE

SEE TABLE 5.2

SEE TABLE 5.2

TABLE 2.13 DIP Switch Functions