Enclosure data, Table 1.2 208v enclosure data, Physical installation 1 - 3 – Yaskawa E7L Drive Bypass User Manual

Page 15

Advertising
background image

Physical Installation 1 - 3

Enclosure Data

Table 1.2 208V Enclosure Data

Input
Volts

HP

1

Drive

Model

CIMR-

Bypass

2

Model

Number

NEC

FLA

OL

110%
1 min

Heat

3

Loss

Watts

Enclosure Dimensions

4

NEMA 1 & NEMA 12 -FVFF

H W D

inches

Weight

5

of

Assembly

Electrical

Schematic

208

0.5

E7U22P21

E7L_D002

2.4

2.6

68

29.48 19.06 13.66

Dimension Drawing

6

S-5537

115 lbs

E7L-00

0.75

E7U22P21

E7L_D003

3.5

3.8

68

1

E7U22P21

E7L_D004

4.6

5.1

78

2

E7U22P21

E7L_D007

7.5

8.2

110

3

E7U22P21

E7L_D010

10.6

11.7

141

5

E7U23P71

E7L_D016

16.7

18.4

202

7.5

E7U27P51

E7L_D024

24.2

26.6

273

10

E7U27P51

E7L_D030

30.8

33.9

365

127 lbs

15

E7U20111

E7L_D046

46.2

50.8

578

20

E7U20151

E7L_D059

59.4

65.3

653

40.48 25.63 14.66

Dimension Drawing

6

S-5539

208 lbs

25

E7U20181

E7L_D074

74.8

82.3

746

Note 1: Horsepower rating is based on a standard NEMA B 4-pole motor.

Note 2: The underscore position in these model numbers codes for the enclosure type: V = NEMA1, B = NEMA12 FVFF.

Note 3: Heat loss is the amount of heat dissipated by the drive at full load with all standard options available inside the enclosure. Drive heat sink losses are

included in the heat loss data.

Note 4: Height dimension (H) excludes the mounting screw tabs. Depth dimension (D) excludes the disconnect handle.

Note 5: This data represents the total weight with all possible standard options. Weight could be less depending on the options specified.

Note 6: All standard options are available in this size enclosure.

Advertising