B2-09, Motor pre-heat current, Preheat current – Yaskawa E7L Drive Bypass User Manual

Page 217: 0 to100, Programming, B2-10, Motor pre-heat current 2, Preheat current2, 0 to 10, Speed search

Advertising
background image

Parameters A - 5

b2-09

Motor Pre-Heat Current
Preheat Current

Motor Pre-heat current in % of drive rated current. This is used to
keep the motor warm to prevent condensation and is used in
conjunction with a digital input (data = 60).

0 to100

0%

Programming

b2-10

Motor Pre-Heat Current 2
Preheat Current2

Sets the DC preheat current for multi-function output setting 80
(Motor Preheat 2) as a percentage of Motor Rated Current (E2-01).

0 to 10%

5

Programming

Speed Search

b3-01

Speed Search Selection
SpdSrch at Start

Enables/disables and selects the speed search function at start.
0: SpdsrchF Disable - Speed search at start is disabled

(estimated speed method is used at other times)

1: SpdsrchF Enable - Speed search is enabled

(estimated speed method)

2: SpdsrchI Disable - Speed search at start is disabled

(current detection method is used at other times)

3: SpdscrhI Enable - Speed search is enabled

(current detection method)

Estimated Speed Method:
Actual motor speed and direction is estimated, then the motor is
ramped from that speed to the commanded speed.
Current Detection Method:
Current level is monitored while output frequency is ramped down.

0 to 3

2

Programming

b3-02

Speed Search Deactivation
Current
SpdSrch Current

Used only when b3-01 = 3. Sets the speed search operation current
as a percentage of drive rated current.

0 to 200

120%

Programming

b3-03

Speed Search Deceleration
Time
SpdSrch Dec Time

Used only when b3-01 = 3. Sets the deceleration time during speed
search.

0.1 to 10.0

2.0sec

Programming

b3-05

Speed Search Delay Time
Search Delay

Delays the speed search operation after a momentary power loss to
allow time for an external output contactor to re-energize.

0.0 to

20.0sec

0.2sec

Programming

b3-14

Bidirectional Speed Search
Selection
Bidir Search Sel

0: Disabled
1: Enabled

0 or 1

1

Programming

Delay Timers

b4-01

Timer Function ON-Delay
Time
Delay-ON Timer

Used in conjunction with a multi-function digital input and a
multi-function digital output. This sets the amount of time between
when the digital input is closed, and the digital output is energized.

0.0 to

3000.0

0.0sec

Programming

b4-02

Timer Function OFF-Delay
Time
Delay-OFF Timer

Used in conjunction with a multi-function digital input and a
multi-function digital output. This sets the amount of time the
output stays energized after the digital input is opened.

0.0 to

3000.0

0.0sec

Programming

PI Control

b5-01

PI Mode Setting
PI Mode

This parameter enables / disables the closed loop (PI) controller.
0: Disabled
1: Enabled (commanded speed becomes PI setpoint)
3: Fref+PI

0, 1, 3

0

Quick Setting

b5-02

Proportional Gain Setting
P Gain

Sets the proportional gain of the PI controller.

0.00 to

25.00

2.00

Quick Setting*

b5-03

Integral Time Setting
PI I Time

Sets the integral time for the PI controller. A setting of zero
disables integral control.

0.0 to 360.0

5.0sec

Quick Setting*

b5-04

Integral Limit Setting
PI I Limit

Sets the maximum output possible from the integrator. Set as a %
of fmax.

0.0 to
100.0

100%

Programming

b5-06

PI Output Limit
PI Limit

Sets the maximum output possible from the entire PI controller.
Set as a % of fmax.

0.00 to

100.0

100.0%

Programming

b5-07

PI Offset Adjustment
PI Offset

Sets the amount of offset of the output of the PI controller. Set as a
% of fmax.
The PI Offset Adjustment parameter has two different uses.
Parameter b5-07 serves different functions depending on whether it
is used on a standard PI loop or a Differential PI loop.
1: Parameter b5-07 causes an offset to be applied to the output of

the PI function in a non-Differential PI loop. Every time the PI
output is updated, the offset is summed with the PI output. This
can be used to artificially kick-start a slow starting PI loop.

2: If the Drive is configured for Differential PI Regulation

(H3-09=16), then the PI Offset is the targeted maintained differ-
ential between the signal measured on analog input A1 and the
signal measured on analog input A2.

–100.0 to

+100.0

0.0%

Programming

Denotes that parameter can be changed when the drive is running. * Menu location is Quick Setting when b5-01=1, and Programming when b5-01=0.

Table A.1 Parameter List (Continued)

Parameter

No.

Parameter Name

LCD Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Advertising