Programming 5 - 50

The Drive has five multi-function contact digital inputs. By programming parameters H1-01 through H1-05, the user can assign
specific functions to each input. Below is a table with a complete list of all of the digital input functions. The programming
manual has a more detailed description of each of the functions.

Following are descriptions of only those parameters that are required for Bypass operations and PI control.

Function: Multi-step Ref 1

Setting: 3

Function: Multi-step Ref 2

Setting: 4

The Drive can be programmed to step through four preset speeds and a jog. It is also possible to mix in the analog inputs as
speed references that can be chosen in place of the first and second preset frequency references. The selection of which preset
speed will be the active speed command is determined by the status of the digital inputs set for Multi-step Ref 1 (H1-0x= 3)
and Multi-step Ref 2 (H1-0x= 4). Changing the active speed command via the Multi-step References can be done while the
Drive is running.

Table 5.10 Digital Input Functions

Parameter

setting

Function

Parameter

setting

Function

0

3-Wire Control

1C

Trim Control Increase

1

Local/Remote Selection

1D

Trim Control Decrease

2

Option/Inv Selection 1

1E

Reference Sample Hold

3

Multi-step Reference 1

20-2F

External Fault

4

Multi-step Reference 2

30

Integral Reset

6

Jog Frequency Reference 1

31

Integral Hold

7

Multi-Accel/Decel 1

34

PI Soft Start Cancel

8

External Baseblock N.O.

35

PI Input Characteristic

9

External Baseblock N.C.

36

Option/Inv Selection 2

A

Accel/Decel Ramp Hold

60

Motor Pre-heat

C

Terminal A2 Enable

61

Speed Search 1

F

Terminal Not Used

62

Speed Search 2

10

MOP Increase

64

Speed Search 3

11

MOP Decrease

67

Communications Test Mode

12

Forward Jog

68

High Slip Braking

13

Reverse Jog

69

Jog Frequency Reference 2

14

Fault Reset

6A

Drive Enable (Cycle Run)

15

Fast Stop N.O.

6B

Com/Inv Selection

17

Fast Stop N.C.

6C

Com/Inv SEL 2

18

Timer Function

6D

Auto Mode @ Close

19

PI Disable

6E

Hand Mode @ Close

1B

Program Lockout

70

Drive Enable (Accept Run)