Programming 5 - 6 – Yaskawa E7L Drive Bypass User Manual

Page 98

Advertising
background image

Programming 5 - 6

Definitions:
L = LonWorks Option Card

* = The Drive factory default

J = Native Protocol, Metasys N2

# = The H/O/A selector keys must have AUTO selected

P = Pneumatic Interface (3 to 15 PSIG)

to allow serial com. to control the Drive

U = Native Protocol, APOGEE FLN

@ = Don’t care

V = Native Protocol, Modbus

Parameter Reference:
b1-01:

Speed Command Input Source

H5-02:

Communication Speed Selection

0: Operator

3: 9600 Baud (default)

1: Terminals (default)

2: 4800 Baud

H1-02:

Drive Terminal S4 Function Selection

H5-07:

RTS Control Selection

3: Multi-step Ref 1

0: Disabled (RTS always on)

14: Fault Reset (default)

1: Enabled (RTS on only when sending) (default)

H1-03:

Drive Terminal S5 Function Selection

H5-08:

Communication Protocol Selection

3: Multi-step Ref 1 (default)

0: Modbus (default)

6C: Com/Inv Sel 2

1: N2 (Metasys)

H3-08:

Drive Terminal A2 Signal Level

2: FLN (APOGEE)

0: 0 - 10 VDC

d1-01:

Frequency Reference 1

2: 4 - 20 mA (default)

d1-02:

Frequency Reference 2

H3-09:

Drive Terminal A2 Function Selection
0: Frequency Bias
2: Aux Reference (default)

DIP Switch Reference:
S1-1:

Terminating resistor, always on for option L, otherwise on only if last device.

S1-2:

Drive Terminal A2 signal level
On = 4-20 mA Off = 0-10 VDC

S4-2:

Drive input terminal S4 operation
On = Input S4 operates inversely with input S5
Off = Inputs S4 and S5 operate independently

Notes:
Hand mode run/stop for Drive and Bypass is always via the front control panel HAND selector key.
Auto mode run/stop for Drive and Bypass without serial com. is from terminal TB1-2.
Auto mode run/stop with serial com. is from serial com. for both Drive and Bypass modes.
DIP switch configurable terminal TB3-3 is connected to Drive terminal A2 (the default). See Chapter 2 Table 2.8 for the alternate TB3-3 configuration.
A Jumper is required from TB5-2 to TB5-7. This is essential for serial com. applications and benign for all other applications.

Table 5.2 Option Dependent Bypass Parameter Settings

Options

Specified

Parameters Effected by Options Specified and Settings

PCB DIP

Switch S1

1 2

PCB DIP

Switch S4

2

HAND Speed

Command

Source

Drive Terminal A2 Sig-

nal Level via TB3-3 or

TB5-9

AUTO

b1-01

H1-02

(S4)

H1-03

(S5)

H3-08 H3-09 H5-2 H5-7 H5-8

Keypad

d1-01 d1-02

4-20

mA

0-10

VDC

3-15

PSIG

Run/Stop

Speed

Terminal

TB1-2

Serial #

TB3-3

(A2)

Serial #

None

1*

14*

3*

2*

0

@

@

@

@ On*

Off*

X

X

X

X

None

1

14

3

0

0

@

@

@

@

Off

Off

X

X

X

X

P

1

14

3

2

0

@

@

@

@

On

Off

X

X

X

X

X

J

0

14

6C

@

@

3*

1*

1

Off* @

Off

X

X

X

U

0

14

6C

@

@

2

1

2

Off

@

Off

X

X

X

V

0

14

6C

@

@

3

1

0*

Off

@

Off

X

X

X

J

0

3

6C

0

2*

3

1

1

Off Off

On

X

X

X

X

U

0

3

6C

2

2

2

1

2

Off

On

On

X

X

X

X

V

0

3

6C

0

2

3

1

0

Off Off

On

X

X

X

X

X

J & P

0

3

6C

2

2

3

1

1

Off

On

On

X

X

X

X

X

U & P

0

3

6C

2

2

2

1

2

Off

On

On

X

X

X

X

X

V & P

0

3

6C

2

2

3

1

0

Off

On

On

X

X

X

X

X

L

0

14

6C

@

2

3

0

0

On

@

Off

X

X

X

X

L

0

3

6C

0

2

3

0

0

On

Off

On

X

X

X

X

L & P

0

3

6C

2

2

3

0

0

On

On

On

X

X

X

X

X

Advertising