Sequence, B1-01, Frequency reference – Yaskawa E7L Drive Bypass User Manual

Page 216: Selection, Reference source, Operator - digital preset speed d1-01, Serial com - rs-485 terminals r+, r-, s+ and s, Option pcb - option board connected at 2cn, 0 to 3, Quick setting

Advertising
background image

Parameters A - 4

Sequence

b1-01

Frequency Reference
Selection
Reference Source

Selects the speed command (frequency reference) input source.
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2 see

parameter H3-13)

2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN

0 to 3

1

Quick Setting

b1-02

Run Command Selection
Run Source

Selects the run command input source.
0: Operator - "Hand" and "Off" keys on digital operator
1: Terminals - Contact Closure on Terminal S1
2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN

0 to 3

1

Quick Setting

b1-03

Stopping Method Selection
Stopping Method

Selects the stopping method when the run command is removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast w/Timer (A new run command is ignored if input before

the time in C1-02 expires)

0 to 3

0

Quick Setting

b1-04

Reverse Operation Selection
Reverse Oper

Determines the forward rotation of the motor, and if reverse
operation is disabled.
0: Reverse Enabled
1: Reverse Disabled
2: Exchange Phase - Change direction of forward motor rotation
3: Exchange Phase, Reverse Disabled - Change direction of

forward motor rotation and disable reverse operation

0 to 3

1

Programming

b1-07

Local/Remote Run Selection
LOC/REM RUN Sel

0: Cycle External RUN - If the run command is closed when

switching from hand (local) mode to auto (remote) mode, the
drive will not run

1: Accept External RUN - If the run command is closed when

switching from hand (local) mode to auto (remote) mode, the
drive WILL run

0 or 1

0

Programming

b1-08

Run Command Selection
During Program
RUN CMD at PRG

0: Disabled - Run command accepted only in the operation menu.
1: Enabled - Run command accepted in all menus

(except when b1-02 = 0)

0 or 1

0

Programming

b1-11

Drive Delay Time Setting
Wait to Run Time

After a run command, drive output will start after this delay time.

0 to 600

0sec

Programming

b1-12

Hand Frequency Reference
Selection
HAND Fref Source

Selects the speed command input source in hand mode.*
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2 see

parameter H3-13)

0 or 1

0

Programming

b1-13

HAND/AUTO During Run
Selection
HAND/AUTO @Run

Selects if drive will permit switching between HAND and AUTO
modes while running.
0: Disabled
1: Enabled

0 or 1

0

Programming

b1-14

Emergency Override Speed
E Override Speed

Sets the speed command used in emergency override mode when
b1-15=0.

0.00 to

120.00 Hz

0.00

Programming

b1-15

Emergency Override

Reference Selection
E OverrideRefSel

Selects the emergency override reverse source.
0: Use b1-14 Ref
1: Use AUTO Ref

0 or 1

0

Programming

DC Braking

b2-01

DC Injection Braking Start
Frequency
DCInj Start Freq

Sets the frequency at which DC injection braking starts when ramp
to stop (b1-03 = 0) is selected. If b2-01< E1-09, DC Injection
braking starts at E1-09.

0.0 to 10.0

0.5Hz

Programming

b2-02

DC Injection Braking
Current
DCInj Current

Selects the DC injection braking current as a percentage of the
Drive rated current.

0 to 100

50%

Programming

b2-03

DC Injection Braking Time at
Start
DCInj Time @Start

Sets the time length of DC injection braking at start in units of 1
second.

0.00 to

10.00

0.00sec

Programming

b2-04

DC Injection Braking Time at
Stop
DCInj Time @Stop

When b1-03 = 2 actual DC Injection time is calculated as follows:
b2-04 * 10 * Output Frequency / E1-04. When b1-03 = 0, this
parameter determines the amount of time DC Injection is applied to
the motor at the end of the decel ramp. This should be set to a
minimum of 0.50 seconds when using HSB. This will activate DC
injection during the final portion of HSB and help ensure that the
motor stops completely.

0.00 to

10.00

0.00sec

Programming

* If b1-13=1, this parameter instead selects whether the AUTO reference is retained as the new HAND reference (setting=0), or the drive will ramp from the AUTO

reference to the existing HAND reference (setting=1).

Table A.1 Parameter List (Continued)

Parameter

No.

Parameter Name

LCD Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location