Specifications C - 2

Standard Drive and Bypass Specifications

The standard Drive and Bypass specifications are listed in the following tables.

208-240 VAC

Table C.1 208-240VAC Drive and Bypass Specifications

Bypass Model Number E7L_ *

D003

D004

D007

D010

D016

D024

D030

D046

D059

D074

D088

Motor HP

208V

0.5/0.75

1

1.5/2

3

5

7.5

10

15

20

25

-

240V

0.5/0.75

1

1.5/2

3

5

7.5

10

15

20

25

30

Bypass rated output current (A)

3.5

4.6

7.5

10.6

16.7

24.2

30.8

46.2

59.4

74.8

88

Drive Model Number CIMR-E7U

22P2

22P2

22P2

22P2

23P7

25P5

27P5

2011

2015

2018

2022

Drive rated output capacity (kVA)

1.4

1.8

3.0

4.1

6.4

8.8

12.0

18.0

23.0

29.0

34.0

Drive rated output current (A)

3.6

4.6

7.8

10.8

16.8

23.0

31.0

46.2

59.4

74.8

88.0

Drive max. output voltage (V)

3-phase; 200, 208, 220, 230, or 240VAC (Proportional to input voltage)

Drive max. output frequency (Hz)

120 Hz

Rated voltage (V)
Rated frequency (Hz)

3-phase, 200/208/220/230/240VAC, 50/60 Hz

Rated input current (A)

4.3

5.5

9.4

13

20

24

37

53

70

89

98

Allowable voltage fluctuation

+ 10%, - 15%

Allowable frequency fluctuation

±5%

Measures for
power supply
harmonics

DC Reactor

Optional

Built-in

12-Pulse
Rectification

Not possible

Possible

Note: The maximum applicable motor output is given for a standard 4-pole motor. When selecting the actual motor and Drive, be sure that the Bypass and

Drive's rated output current is equal to, or greater than, the motor's rated current.

A phase-shifting transformer is required on the power supply for 12-pulse rectification.
* Only 208V model numbers are shown.