E1-05 maximum output voltage, E1-06 base frequency, E1-07 mid output frequency a – Yaskawa E7L Drive Bypass User Manual

Page 138: E1-08 mid output voltage a, E1-09 minimum output frequency, E1-10 mid output voltage, E1-11 mid output frequency b, E1-12 mid output voltage b

Advertising
background image

Programming 5 - 46

E1-05 Maximum Output Voltage

Setting Range:

0.0 to 255.0V (208V/240V Models)
0.0 to 510.0V (480V Models)

Factory Defaults: 208.0V (208V Models)

230.0V (240V Models)
460.0V (480V Models)

E1-06 Base Frequency

Setting Range:

0.0 to 200.0 Hz (settings above 120.0 Hz are currently not supported)

Factory Default: 60.0 Hz

E1-07 Mid Output Frequency A

Setting Range:

0.0 to 200.0 Hz (settings above 120.0 Hz are currently not supported)

Factory Default: 3.0 Hz

E1-08 Mid Output Voltage A

Setting Range:

0.0 to 255.0V (208V/240V Models)
0.0 to 510.0V (480V Models)

Factory Defaults: 18.0V (208V Models)

18.0V (240V Models)
33.6V (480V Models)

E1-09 Minimum Output Frequency

Setting Range:

0.0 to 200.0 Hz (settings above 120.0 Hz are currently not supported)

Factory Default: 1.5 Hz

E1-10 Mid Output Voltage

Setting Range:

0.0 to 255.0V (208V/240V Models)
0.0 to 510.0V (480V Models)

Factory Defaults: 10.8V (208V Models)

10.8V (240V Models)
16.8V (480V Models)

E1-11 Mid Output Frequency B

Setting Range:

0.0 to 200.0 Hz (settings above 120.0 Hz are currently not supported)

Factory Default: 0.0 Hz

E1-12 Mid Output Voltage B
E1-13 Base Voltage

Setting Range:

0.0 to 255.0V (208V/240V Models)
0.0 to 510.0V (480V Models)

Factory Defaults: 0.0V (208V Models)

0.0V (240V Models)
0.0V (480V Models)