Motor setup, E2-01, Motor rated current – Yaskawa E7L Drive Bypass User Manual

Page 223: Motor rated fla, Set to the motor nameplate full load amps, 10% to, Kva dependent, Quick setting, E2-03, No-load current

Advertising
background image

Parameters A - 11

Motor Setup

E2-01

Motor Rated Current
Motor Rated FLA

Set to the motor nameplate full load amps.

10% to

200%

kVA

Dependent

Quick Setting

E2-03

No-Load Current

Sets the magnetizing current of the motor.

kVA

Dependent

kVA

Dependent

Programming

E2-05

Motor Line-to-Line
Resistance
Term Resistance

Phase to phase motor resistance, normally set by the autotuning
routine.

0.000 to

65.000

kVA

Dependent

Programming

Com OPT Setup

F6-01

Operation Selection after
Communication Error
Comm Bus Flt Sel

Sets the stopping method for option PCB communications error
(BUS fault). Active only when a communications option PCB is
installed and when b1-01 or b1-02 = 3.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

1

Programming

F6-02

Detection Selection of Exter-
nal Fault from Communica-
tion Option Card
EF0 Detection

0: Always detected
1: Detected only during run

0 or 1

0

Programming

F6-03

Stopping Method for
External Fault from
Communication Option Card
EF0 Fault Action

0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

1

Programming

F6-05

Current Monitor Display Unit
Selection
Current Unit Sel

0: A Display (Amps Display)
1: 100%/8192 (Drive Rated Current)

0 or 1

0

Programming

Table A.1 Parameter List (Continued)

Parameter

No.

Parameter Name

LCD Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Advertising