Programming 5 - 52

To switch the command source between the serial communication port and the control circuit terminals be sure to program the
following parameters:

Set b1-01 (Frequency Reference Selection) to 1 (Terminals).

Set b1-02 (Run Command Selection) to 1 (Terminals).

Set H1-0x (Input Terminal Function Selection) to 6B or 6C.

The Com/Inv Sel 2 function will operate the same way except the logic is reversed. When a digital input is programmed for the
Com/Inv Selection function (H1-0x= 6C) that input will function as follows:

Table 5.12

Option/Inv Function Input Status

Run and Speed Command Source

OPEN

From the control circuit and analog input terminals

CLOSED

From Serial Com port (R+,R-,S+, and S-) (embedded protocols)

Table 5.13

Option/Inv Function Input Status

Run and Speed Command Source

OPEN

From Serial Com port (R+, R-, S+, and S-) (embedded protocols)

CLOSED

From the control circuit and analog input terminals

IMPORTANT

Switching the Reference and Run sources can only be done while the Drive is stopped.