3.5.3 Activating the external relays

The relays can be configured in the system configuration under Digital I/O

Relays.

The name, hold time and manual control for each relay can be configured here, as can the
“Manual Reset” and “Hold” options. More details on these points can be found below.

Hold time:

The hold time specifies how long the relay should be closed when used with edge control.

Manual control:

Level:

When the relay contact is used with level control, the contact remains closed until opened
manually by the user.

Edge:

When the relay contact is used with edge control, the contact remains closed until the set hold
time has expired.


Manual reset:

When this option is activated, a relay which has been closed by an activation can be reopened
manually by a user.

Hold:

When this option is used, the relay remains closed when it has been activated by a remote
user over the network and the system connection has been terminated.

Note:

The “Edge control” and “Level control” options can also be set for the relay in the activation.
When creating the activation, ensure that the same control mode is used as on the relay.