Programming – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 100

Advertising
background image

100

MultiPump – Slave Pump Control

14. Once you have saved the parameter 1506, press the EXIT

key. Use down arrow until you highlight parameter group 18
“RELAY OUTPUTS”. Then press the SEL key.

15. After above step, you should have parameter 1801 “RELAY

OUTPUT 1” highlighted. Press the EDIT once. Uses the up
arrow to highlight “START SLV”, then press SAVE.

16. Use the down arrow to highlight parameter 1802 “RO 1 ON

DELAY”, then press EDIT. Use the UP arrow to set your time
delay to TURN ON RELAY 1 in seconds. Then press the SAVE
key. NOTE: You may have to adjust this time delay based

on your system.

17. Once parameter 1802 has been saved, use the DOWN

arrow to highlight parameter “1803 RO 1 OFF DELAY”, then
press the EDIT key. Use the UP arrow to select the OFF
DELAY for relay 1 in seconds. Press the SAVE key. This will
allow a timed delay when relay 1 turns off the first slave
pump.

18. If you do not require other SLAVE relays, then proceed to the next step MULTIPUMP

CONTROL. If more relays are required, repeat steps above for RELAY 2 and RELAY 3,
parameters 1804, 1805, 1806, 1807, 1808.

19. Once you have saved your last relay output, press the EXIT

key once. Use the down arrow until you highlight parameter
group 22 “MULTIPUMP CTRL”, then press SEL key.

20. After above step, highlight parameter 2201 VALUE

DECREASE, then press EDIT. Use arrows to program the
required pressure drop allowed by the Aquavar pump,
before the first slave pump turns on. Press the SAVE key.

NOTE: Keep this pressure low enough from the Aquavar

pressure setting and adjust your relay ON TIME DELAY to

PREVENT PUMP “CYCLING”!

EXIT

SEL

REM

PAR GROUPS

18

14 SPD LIM/STRT LEVL

15 XDUCER VARIABLES

16 REFERENCE SELECT

18 RELAY OUTPUTS

19 ANALOG OUTPUTS

EXIT

EDIT

REM

PARAMETERS

1801 RELAY OUTPUT 1

NOT SEL

1802 R01 ON DELAY

1803 R01 OFF DELAY

1804 RELAY OUTPUT 2

EXIT

EDIT

REM

PARAMETERS

1801 RELAY OUTPUT 1

1802 R01 ON DELAY

10.0 s

1803 R01 OFF DELAY

1804 RELAY OUTPUT 2

EXIT

EDIT

REM

PARAMETERS

1801 RELAY OUTPUT 1

1802 R01 ON DELAY

1803 R01 OFF DELAY

5.0 s

1804 RELAY OUTPUT 2

PROGRAMMING

EXIT

SEL

REM

PAR GROUPS

22

16 REFERENCE SELECT

18 RELAY OUTPUTS

19 ANALOG OUTPUTS

21 REGULATE

22 MULTIPUMP CTRL

EXIT

EDIT

REM

PARAMETERS

2201 VALUE DECREASE

2.1 PSI

2202 VALUE INCREASE

2203 ENABLE SEQUENCE

2204 SWITCH LEAD/LAG

Advertising