Wiring IP 21 / UL Type 1 Enclosure with Conduit

1. Open the appropriate knockouts in the conduit/

gland box.

2. Install thin-wall conduit clamps (not supplied).

3. Install conduit/gland box.

4. Connect conduit runs to box. Always follow

appropriate NEC or local electrical codes for inverter
drives, motor wiring.

5. Route input power and motor wiring through

conduits. Preferably metal, grounded type.

6. Strip wires.

7. Connect power, motor, and ground wires to the drive

terminals. See “Power Connections” on page 29.

8. Route the control cable, transducer cable through the

conduit.

9. Strip the control cable sheathing and twist the copper

screen into a pigtail.

10. Connect the transducer screen pigtail for digital and

analog I/O cables at X1-1.

11. Strip and connect the individual control wires to the

drive terminals. See “Control Connections” on page
29. Including transducer.

12. Install the conduit/gland box cover (1 screw).

13. Wire transducer leads to analog 2, terminal(s) +24V,

AI2 and GND.

14. Wire positive lead of transducer to terminal 10

(+24VDC). Color is red or brown.

15. Wire analog lead (negative) to terminal 10 of X1 for

4-20mA signal. Color is white or black.

16. Take the transducer cable screen to X1, #1 Terminal.

INSTALLATION