Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 69

Advertising
background image

69

Defaults
Group

Fault Range Description

Single Synch- Multi- Constant Speed

24

Functions

Pump ronous Control Slave Control

2409 Comm Fault

Selects how the drive reacts in a Last

Last

Last

Last

Last

Function

fieldbus comm break i.e.; if the Speed Speed Speed

Speed

Speed

drive fails to receive command

word or reference. The time de-

lays is given by parameter 2410.

Not Selected No response

Fault

Drive Faults and coasts to stop

Last Speed

Drive displays a warning and

remains running at last speed

reference.

2410 Comm Fault

0…60.0s

Defines the time delay for the

3.0 s

3

3

3

3

Time

control word or reference

supervision.

Group

Automatic

Range Description

Single Synch- Multi- Constant Speed

25

Reset

Pump ronous Control Slave Control

2501 NR of Trials

0…5

Sets the number of allowed

0

0

0

0

0

automatic resets within a trial

period defined by parameter

2502.

2502 Trial Time

1.0…600.0 s

Sets the time limit used for

30 s

30 s

30 s

30 s

30 s

counting and limiting the

number of resets.

2503 Delay Time

0.0…120.0 s

Sets the delay between fault

0 s

0 s

0 s

0 s

0 s

detection and attempted drive

restart.

2504 AR Overcurrent

Auto reset after overcurrent

Enabled Enabled Enabled Enabled Enabled

Disable

fault.

2505 AR Overvoltage

Auto reset of overvoltage

Enabled Enabled Enabled Enabled Enabled

Disable

fault.

2506 AR Undervoltage

Auto reset for undervoltage

Enabled Enabled Enabled Enabled Enabled

Disable

of drive.

2507 AR AI<Min

Auto reset after transducer

Enabled Enabled Enabled Enabled Enabled

Disable

signal loss.

Group

Energy

Range Description

Single Synch- Multi- Constant Speed

26

Savings

Pump ronous Control Slave Control

2601 Energy Cost

0.000…1.000 Cost of energy in USD

2602 Baseline Power 0…1000 hp

Baseline HP for a conventional

fixed speed system.

2603 Savings Scale

0…65535

This parameter scales the

10000 10000 10000 10000 10000

analog output when energy

savings is selected.

2604 Energy Save

Savings Savings Savings Savings Savings

Methd

Savings Op 1

Op 1

Op 1

Op 1

Op 1

Op 1

Savings Op 2

PARAMETER LISTINGS