Defaults
Group Status Words

Range

Description

Single Synch- Multi- Constant Speed

03

Pump ronous Control Slave Control

0310 AV Alarm Word

Aquavar Alarm word

0311 AV Fault Word

Aquavar Fault word

0312 Comm RO Word

0313 Comm Value 1

0314 Comm Value 2

Group

Locks/

Range Description

Single Synch- Multi- Constant Speed

10

Passwords

Pump ronous Control Slave Control

1001 Parameter Lock

Selects the state of the parameter Locked Locked Locked Locked Locked

lock. The lock prevents

parameters from being changed.

Open

The lock is open. Parameter

values can be changed.

Locked

Parameter values cannot be

(Default)

changed from the keypad. The

lock can be opened by entering

the valid password in parameter

10.02. When the keypad is

locked the AV keypad function-

ality is limited to starting,

stopping and changing the

reference (set point).

1002 Pass Code

0…300000

Password setting 66 opens the

0 0 0 0 0

lock and returns the value to

zero on the display. The pass-

word relocks when power is

disconnected. To relock the

keypad reset parameter 1001

to “Locked”.

1003 Local Lock

Disables local control on the

Off Off Off Off Off

keypad. WARNING! Before

activating, ensure that the

control panel is not needed for

stopping the drive.

Off (Default)

Local control allowed.

On

Local control disabled.

1004 Parameter Save

Saves the parameter values to

Done Done

Done

Done

Done

the permanent memory.

Done (Default) Parameters entered via the

keypad are automatically saved.

Parameters are not automatically

saved when altered through the

fieldbus connection.

PARAMETER LISTINGS