Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 59

Advertising
background image

59

Defaults
Group

Spd Lim/ Range

Description

Single Synch- Multi- Constant Speed

14

Strt/Lvl

Pump ronous Control Slave Control

1407 Priming Delay

0…6000 s

When the drive is starting from

0

0

0

0

0

0 RPM this parameter delays

pump protection faults (2404

and 2407) for the setting time.

The default setting is “0”. Once

the priming delay time is

complete the protection delay

(parameter 2406) becomes

functional. During the priming

delay the pump runs at the

maximum speed setting

(parameter 1401) since it

cannot achieve the set point.

Group Transducer

Range Description

Single Synch- Multi- Constant Speed

15

Var

Pump ronous Control Slave Control

1501 Transducer Unit

Selects the units (default is

Psig

Psig

Psig

Psig

Psig

pressure) for the primary process

transmitter feedback located at

AI2. In speed control macro

default unit is RPM.

%

GPM

Psig (Default)

Ft

F Deg

C Deg

1502 Transducer Max 0…6553.5

For single pump and multipump

300

300

300

300

60

macros this parameter defines

the full-scale feedback (20 mA

setting) of the primary process

transmitter at AI2. This parameter

also correlates to the maximum

value of Reference (set points) 1

and 2. For the Speed Control

macro this parameter scales the

maximum (20 mA or keypad )

speed setting. Note when units

are in Ft, M, In or Cm: AI2 Max

is always based on a specific

gravity = 1 regardless of setting

for parameter 1506. Actual

pressure signals in Ft, M, In or

Cm are corrected for specific

gravity by the firmware. Signal

can be quadratic or linear.

PARAMETER LISTINGS