Programming, Multipump – slave pump control – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 101

Advertising
background image

101

MultiPump – Slave Pump Control

21. Once previous step has been saved, use the Down Arrow

and highlight parameter “2203 ENABLE SEQUENCE”, then
press EDIT. Using the up or down arrow, enter the frequency
in Hertz (HZ) that you wish the SLAVE pump will turn on once
the lead pump reaches this speed. Default is set for 59 HZ
and is typical for 60HZ systems. If you change this setting,
press the SAVE key. If no changes are required, then press
the EXIT key.

22. Group 2205 – Enter frequency for slave pump to be turned off.

23. Final step is to enter your required pressure in

the system. After above programming has been
completed, press the EXIT key two (2) or three
(3) times, until you arrive back to the first control
display screen. (SEE DIAGRAM) Then press the
UP or DOWN arrow to select the required system
pressure for your Aquavar controlled pump. Once
pressure has been selected, press the green
START key on the keypad.

24. Optional Step: To lock out access to the control

panel (keypad), refer to page 104. This will prevent
unauthorized users from changing programming.

NOTE: If an error or fault occurs, refer to the faults/alarms section of this manual, page
115. When troubleshooting an Aquavar system, always break down into the following
components:

1. Aquavar programming — check default settings recommended for single pump, multi-

pump, slave pump etc.

2. Electrical supply/ motor/ wiring/grounding — check your supply voltage, motor

wiring, transducer wiring, and grounding.

3. Mechanical/Pump/ Rotation — check your pump rotation, rubbing or other mechanical

problems. Pump “ run out”.

4. Hydraulic System/ Piping — check to ensure proper suction and ischarge piping layout,

proper NPSHa, air entrainment, vortex, friction loss, system curve compensation etc.

5. Environment — protect from high temperatures, direct sun, freezing temperatures, high

altitude, dust, vibration, lack of air flow.

EXIT

EDIT

REM

PARAMETERS

2201 VALUE DECREASE

2202 VALUE INCREASE

2203 ENABLE SEQUENCE

59.00 HZ

2204 SWITCH LEAD/LAG

PROGRAMMING

DIR

MENU

REM

27.8%

LOC

REM

Status

LED

UP

SOFT

KEY 1

DOWN

LOC/REM

STOP

START

HELP

SOFT

KEY 2

40.2 PSI

sp

0.0 PSI

ac

0.0 HZ