Minimum Speed Options

(continued)

Parameter

Name

Value/Range

Note(s)

14.03

CONFIG

SPD=MINSPD

Selecting SPD=MINSPD will result in the drive

SPEED MIN

SPD=0 [default]

staying at minimum speed until it is manually

shut-off, process demand increases, a secondary

protection fault is cleared, or a pump protection

fault forces it to shutdown.If SPD=0 is selected,

the drive will stop.

14.04

STP DELAY

0-1800 sec

This parameter enables the drive to remain at

MIN SPD

0 (default)

minimum speed for a period (up to 1800

seconds) before shutting down.

14.05

RESTART

0.0-150%

If the drive is shutdown by CONFIG SPEED MIN

VALUE

0 (default)

(14.03) due to no system demand (pressure

control and level control modes only) the drive

will sleep until the process actual value drops

below a set restart value (14.05) for longer than

the restart delay (14.06). If operating in inverse

mode (21.01) the drive will sleep until the

process variable rises above the restart value.

Wake-up level in % of setpoint value = 0 – 150%.

Default is 0%. To disable the Restart Value

function enter “0%”.

14.06

RESTART

0-3600 Sec

This is the length of time the drive waits

DELAY

0 (default)

between starting the pump according to

1405 value.

12.02

AUTO

OFF (default)

This enables the drive to restart on its own

RESTART

ON

following a power failure or ERROR RESET.

24.06

ERROR

0 (Default)

If the Aquavar unit faults on Pump Protection,

RESET

1-9999

this parameter will reset the fault up to the

selected number of times before completely

shutting off the drive.

24.07

RESET

0-250 seconds

The automatic reset of protection faults can be

DELAY

60 seconds (Default)

delayed. Default value is 60 seconds.

Restart Value
Allows a pressure or value drop before the Aquavar starts to maintain system pressure. Units
are in % of set value. (e.g. If set pressure is 100 PSI and 14.05 is set for 90%, then the Aquavar
will wait until system pressure drops to 90 PSI before starting.)

Priming Delay
This feature will override the PUMP PROTECT feature and is designed to allow self-priming

pumps sufficient time to prime before the Aquavar Pump Protection logic becomes active.

The delay period is applied only if the pump is being started from a zero-speed condition.

Once the priming delay is complete, the PROTECTION DELAY (24.06) becomes active, if set.

Parameter

Name

Value/Range

Note(s)

14.07

PRIMING

0-6000 Seconds

The priming delay time is added to the

DELAY

0 (Default)

pump protection delay time.

NOTE: Do not set beyond normal priming time for specific pumps or damage may occur.
Refer to pump manufacturer for maximum allowed priming times before shutdown.