Programming, Multipump – constant pressure control – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual

Page 93

Advertising
background image

93

MultiPump – Constant Pressure Control

18.

After 2203 has been selected, press the down arrow to

highlight parameter 2204 “SWITCH LEAD LAG”. Press
the EDIT key once. Using the up or down arrows, select
the alternating time between lead and lag pumps. Once
selected, press the SAVE key.

19.

Once 2204 has been saved, press the down arrow to

highlight “2207 PUMP ADDRESS”. Press the EDIT key once.
Use the up arrow to select your appropriate address for
each pump. Always start with address one. Once each
pump has a different address, press the SAVE key.

20. Final step is to enter your required system

pressure. After above programming has been
completed for each Aquavar controlled pump,
press the EXIT key two (2) or three (3) times, until
you arrive back to the first control display screen.
(SEE DIAGRAM.) Then press the UP or DOWN
arrow to select the required system pressure for
your Aquavar controlled pump. Once pressure has
been selected, press the green START key on the
keypad.

21. Optional Step: To lock out access to the control

panel (keypad), refer to page 104. This will prevent
unauthorized users from changing programming.

NOTE: If an error or fault occurs, refer to the troubleshooting/faults section of this
manual. When troubleshooting an Aquavar system, always break down into the following
components:

1. Aquavar programming — check default settings recommended for single pump, multi-

pump, slave pump etc.

2. Electrical supply/ motor/ wiring/grounding — check your supply voltage, motor

wiring, transducer wiring, and grounding.

3. Mechanical/Pump/ Rotation — check your pump rotation, rubbing or other mechanical

problems. Pump “ run out”.

4. Hydraulic System/ Piping — check to ensure proper suction and discharge piping

layout, proper NPSHa, air entrainment, vortex, friction loss, system curve compensation
etc.

5. Environment — protect from high temperatures, direct sun, freezing temperatures, high

altitude, dust, vibration, lack of air flow.

EXIT

EDIT

REM

PARAMETERS

2201 VALUE DECREASE

2202 VALUE INCREASE

2203 ENABLE SEQUENCE

2204 SWITCH LEAD/LAG

12 H

EXIT

EDIT

REM

PARAMETERS

2204 SWITCH LEAD/LAG

2205 SYNC LIMIT

2206 SYNC WINDOW

2207 PUMP ADDRESS

0

PROGRAMMING

DIR

MENU

REM

11.1%

LOC

REM

Status

LED

UP

SOFT

KEY 1

DOWN

LOC/REM

STOP

START

HELP

SOFT

KEY 2

40.2 PSI

sp

0.0 PSI

ac

0.0 HZ